NewTrend · PV DC Fuse Holder
Product overview
R-30 is a non-polarized, single-pole DC fuse holder rated up to 1000V DC and 30A. It accepts 10 × 38mm cylindrical fuse links and provides an LED indication of fuse operating status. The hinged carrier supports touch-safe fuse-link replacement and service access in photovoltaic string and inverter circuits.
Key features
- 1000V DC, maximum holder current 30A; non-polarized 1P construction.
- 10 × 38mm cylindrical fuse-link format with LED operating-status indication.
- Touch-safe hinged carrier for fuse-link replacement.
- 35mm DIN-rail mounting for inverter and photovoltaic string protection assemblies.
Technical selection summary
Product identification
| Model | R-30 |
|---|---|
| Poles | 1P |
| Maximum holder current | 30A |
| Rated operational voltage (Ue) | 1000V DC |
| Polarity | Non-polarized |
| Standard | IEC 60947-3 |
| Product-page fuse-link range | 10A to 30A; 10 × 38mm |
| Certification documentation | To be confirmed for the supplied configuration |
Electrical characteristics
| Rated working voltage (Ue) | 1000V DC |
|---|---|
| Rated current values (In), datasheet | 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A, 12A, 15A, 20A, 25A, 30A |
| Breaking capacity, datasheet | 20kA |
| Maximum power dissipation | 3W |
Control and indication
| Operating state / fault indication | Indicator light OFF / indicator light ON |
|---|
Connection and installation
| Wire cross-section | 2.5–25mm² |
|---|---|
| Terminal screws | M5 |
| Tightening torque | 2.5Nm |
| Degree of protection | IP20 |
Installation environment
| Fuse size | 10 × 38mm |
|---|---|
| Operating temperature range (TU) | −40°C to +85°C |
| Mounting rail | TH35-7.5 / DIN35 |
| Pollution degree | 3 |
| Relative humidity | ≤95% at +20°C; ≤50% at +40°C |
| Weight | 0.07kg per pole |
| Installation class | III |
Outline dimensions
| Width | 18mm |
|---|---|
| Overall height | 88mm |
| Overall depth | 74.5mm |
| Rail reference | 35mm |
| Rear and side height references | 83.5mm / 45.5mm |
| Side depth references | 44.3mm / 5.5mm |
The protective characteristic and fault interruption are provided by the selected fuse link. Match the fuse link, holder voltage and current ratings to the circuit. Isolate the circuit before opening the carrier or replacing the fuse.
Typical applications
- Photovoltaic DC string fuse protection.
- Solar inverter DC protection and maintenance assemblies.
- DIN-rail-mounted DC fused distribution circuits.
Download R-30 technical datasheet (PDF)
Installation and fuse replacement

Outline dimensions

Product views