Photovoltaic DC fuse holder
Product overview
The RD-30 is a single-pole photovoltaic fuse holder with a pull-out carrier and a fuse-status indicator window. It accepts a compatible 10 × 38 mm fuse link selected for the circuit voltage, current and prospective fault level.
Technical selection summary
| Model | RD-30 |
|---|---|
| Product type | PV DC fuse holder |
| Utilization category | DC-PV0 |
| Rated operational voltage (Ue) | 1100 V DC |
| Maximum rated holder current | 30 A |
| Manufacturer reference current range | 1–30 A; actual operating current is subject to the selected fuse link and derating |
| Poles | 1P |
| Compatible fuse-link size | 10 × 38 mm |
| Rated insulation voltage (Ui) | 1200 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Maximum acceptable power dissipation | 4 W |
| Ingress protection | IP20 |
| Construction | PA66 housing; pull-out carrier with status window |
| Rated limiting short-circuit current (manufacturer catalogue) | 30 kA with the specified protective arrangement; verify the fuse-link and assembly rating |
| Manufacturer reference standards | IEC/EN 60947-1 and IEC/EN 60947-3 |
Isolate the circuit before opening the fuse carrier or replacing a link. Fuse-link selection determines the protective characteristics of the assembly.
Typical applications
- PV string fuse mounting in combiner boxes and DC distribution enclosures.
- Inverter-side PV DC circuits using a compatible cylindrical fuse link.
Fuse holder and fuse-link reference
| Parameter | RD-30 holder | RF-30 fuse-link reference |
|---|---|---|
| Reference standards | IEC/EN 60947-1; IEC/EN 60947-3 | EN 60269-1; EN 60269-6 |
| Operational voltage | DC 1100 V | DC 1000 V |
| Current range | 1–30 A | 6, 8, 10, 12, 15, 16, 20, 25, 30, 32 A |
| Maximum acceptable power dissipation | 4 W | 4 W |
| Fuse-link dimensions | 10 × 38 mm | 10 × 38 mm |
| Catalogue short-circuit reference | 30 kA, assembly conditions apply | 20 kA, exact link conditions apply |
The fuse-link reference has a lower voltage rating than the holder. Select the complete assembly for the circuit voltage.
Construction and operating features
- Pull-out carrier provides access for replacement of the cylindrical fuse link after circuit isolation.
- Status window provides the manufacturer-described fuse indication.
- PA66 housing and busbar-compatible arrangement support modular PV circuit assembly.
- The selected fuse link provides overload and short-circuit protection within its verified ratings.
Compatible fuse links
The photo illustrates the 10 × 38 mm fuse-link format. Check the exact link voltage and current rating and confirm what is supplied with the holder. The separate RF-30 link shown in the manufacturer comparison table is listed at 1000 V DC, so its voltage rating must be checked against the circuit.
Pull-out carrier and status window
The manufacturer describes the window as an indication of an operated fuse. Isolate the circuit before opening the carrier. Protection functions illustrated in the manufacturer graphic depend on the selected fuse link and circuit. Verify the required protection with the complete assembly.
Material test reference
This manufacturer photograph shows a material test setup. The web graphic and catalogue state different flammability classifications. Confirm the applicable test standard and classification for the supplied assembly.
Product and installation dimensions
PV wiring reference
Conceptual string protection layout. Verify the circuit and protective devices for the actual installation.
Cabinet derating reference
| Adjacent poles | Ambient (°C) | Cabinet temperature (°C) | Derating factor |
|---|---|---|---|
| 1–4 | 25 | 30 | 1.00 |
| 1–4 | 30 | 40 | 0.93 |
| 1–4 | 40 | 50 | 0.90 |
| 1–4 | 50 | 60 | 0.85 |
| 5–24 | −11 | 30 | 0.90 |
| 5–24 | 3 | 40 | 0.85 |
| 5–24 | 18 | 50 | 0.75 |
| 5–24 | 40 | 60 | 0.60 |
| 5–24 | 55 | 65 | 0.50 |
| 5–24 | 60 | 70 | 0.45 |
| 5–24 | 65 | 75 | 0.60 |
Manufacturer reference for a 0.1 m³ cabinet. For assemblies above five poles, the reported reference data were measured with 24 poles energized. Consult the manufacturer for any non-monotonic points and use the verified assembly derating for the installation.