Product overview
The O319G is a three-pole, 63 A manual transfer switch for moving one three-phase load between two supplies — typically an inverter or generator on one side and the city mains on the other. All three poles are switched together by a single handle, so the load cannot be left with one phase still connected to the source it was supposed to be isolated from. The handle has three stable positions — I, centre OFF and II — and the mechanical interlock keeps the two sources apart, so the incoming supplies cannot be paralleled by mistake.
It is the 3P 63 A member of the O119G / O219G family and takes three 18 mm module spaces on the rail. Terminal numbering, handle travel and mounting depth are shared across the 1P, 2P, 3P and 4P versions, so a panel laid out for this device can be extended later without changing the rail layout. The device is marked AC-22A, Ui 690 V, 50/60 Hz, IEC/EN 60947-3 and GB/T 14048.3, and clips onto 35 mm DIN rail.
Three-phase changeover with three switching positions
The switch is built for the two-supply case: mains on one side, inverter or standby supply on the other, and one three-phase load that must never see both at once. The handle sits in the middle of the front face and travels through three detents — I, OFF and II. In the centre position the moving contacts are separated from both sets of fixed contacts, so all three phases are isolated from either source and the gap is visible at the handle.
With the handle at I, terminal 1 is connected to 2, 5 to 6 and 9 to 10. At II, 1 goes to 4, 5 to 8 and 9 to 12. In the middle position all six paths are open. The interlock is mechanical rather than electrical: because the single handle can only be in one position, closing one path physically prevents the other from closing, and the changeover cannot be defeated by a control-circuit fault or by two operators working at once.
Technical data
The figures below are the values published by the manufacturer for this model. Rated voltage is quoted as 240/415 V in the source data sheet — the phase-to-neutral and phase-to-phase values for a three-pole device — while the marking on the supplied unit reads 400 V~; check the marking against the installation before commissioning.
| Model | O319G |
|---|---|
| Product type | Manual transfer switch (MTS), dual-power changeover, disconnectable |
| Poles | 3P |
| Rated current | 63 A (model range 40 A / 63 A) |
| Rated voltage | 240/415 V AC (source data sheet); device marking 400 V~ |
| Frequency | 50/60 Hz |
| Utilization category | AC-22A |
| Contact form | 1-0-2 |
| Insulation voltage (Ui) | 690 V |
| Electrical life | 1500 operations |
| Mechanical life | 8500 operations |
| Protection degree | IP20 |
| Ambient temperature | -5 °C to +40 °C |
| Terminal capacity | 16 mm² |
| Standards | IEC/EN 60947-3, GB/T 14048.3 |
| Mounting | 35 mm DIN rail (EN 60715), fast clip device |
| Terminals | 1, 3, 5, 7, 9, 11 at the top; 2, 4, 6, 8, 10, 12 at the bottom |
| Width | 54 mm (three 18 mm modules) |
Handle, housing and mounting
The operating handle is widened and given a deeper grip than a standard miniature breaker lever, which makes the changeover stroke easier to complete by hand and gives a clearer visual indication of the selected position. All three poles move on the same shaft, so there is no way to operate one pole and leave the others behind.
The body is moulded from a thermosetting plastic rather than a thermoplastic. Thermosets cure into a cross-linked structure, so they do not soften, flow or drip when the terminals run hot; the housing keeps its mechanical strength and its shape at temperatures that would deform an ordinary thermoplastic enclosure. That matters at the point where the cable lug meets the terminal, which is where heat concentrates in a transfer switch used continuously at 63 A.
Installation uses the standard 35 mm rail: the device clips on with the spring-loaded foot at the bottom and is released with a screwdriver in the slot, so it can be fitted or removed without disturbing neighbouring modules. Three module widths keep a three-phase changeover point inside a small part of the enclosure.
Wiring
Terminal numbering follows the device: 1, 3, 5, 7, 9, 11 at the top and 2, 4, 6, 8, 10, 12 at the bottom, with the odd numbers on the line side of each pole and the even numbers on the load side. In position I each pole connects its top terminal to the first pair of bottom terminals; in position II it connects to the second pair; in the centre position both circuits are open.
For dual-power changeover the manufacturer specifies feeding the normal supply and the standby supply from the lower terminals and taking the load from the upper terminals, which is the arrangement drawn on the front face. With the handle at I the load is fed from the normal supply; at II it is fed from the standby supply; at OFF both paths are open and the load is isolated. The incoming and outgoing side can otherwise be arranged to suit the panel, as long as the source and load are never swapped between the two changeover paths.
Dimensions
The 3P unit is 54 mm wide and 84 mm high; the depth over the handle is 75 mm, as marked on the manufacturer’s drawing. Dimensions are measured by hand and are for reference — allow clearance for the handle swing and for the cable bend radius at the terminals.
Markings on the front face
The front carries the terminal numbers 1, 3, 5, 7, 9, 11 at the top and 2, 4, 6, 8, 10, 12 at the bottom, the changeover symbol beside the handle, the model and current rating, the rated voltage and frequency, the CE mark and the standard references. The specification block on the lower half repeats the utilization category AC-22A, the insulation voltage Ui 690 V and the standard numbers, so the ratings can be read with the device installed in a panel.
Typical applications
- Manual changeover between the city mains and a three-phase inverter or generator, with all three phases switched.
- Isolation and source selection on distribution and control panels feeding three-phase loads.
- Load transfer where a visible, lockable disconnect position is required.
- Pumping, ventilation, compressors and small three-phase machines that must not be fed from two sources at once.
- Peak-valley tariff switching and PV self-consumption systems with a grid back-up path.
Manufacturing
The switch is assembled and tested on the manufacturer’s own automated calibration and test lines, with the calibration stations and the moulding shop shown below.
Product reference images and drawings
Manufacturer reference views for the O319G. Check the terminal arrangement and handle positions against the supplied unit.