NewTrend · manual transfer switch (MTS)
Product overview
The O119G is a single-pole, 80 A manual transfer switch for moving one load between two single-phase supplies. The handle has three stable positions — I, centre OFF and II — and the mechanical interlock keeps the two sources apart, so the incoming supplies cannot be paralleled by mistake. The device is a disconnectable changeover switch that clips onto a 35 mm DIN rail and is marked AC-22A, Ui 690 V, 50/60 Hz, GB/T14048.3 and IEC/EN 60947-3.
It is the 1P 80 A member of the O119G family. The same body is used for the 2P, 3P and 4P versions, so the terminal numbering, handle travel and mounting depth are identical across the range and a panel can be built for a single-phase load today and extended later without changing the rail layout.
Dual power isolation with three switching positions
The switch is built for the two-supply case: mains on one side, generator or standby supply on the other, and one load that must never see both at once. The handle sits in the middle of the front face and travels through three detents — I, OFF and II. In the centre position the moving contact is separated from both fixed contacts, so the load is isolated from either source and the gap is visible at the handle.
The interlock is mechanical rather than electrical. Because the single handle can only be in one position, closing one path physically prevents the other from closing, and the changeover cannot be defeated by a control-circuit fault or by two operators working at once.
Technical data
The figures below are the values published by the manufacturer for this model. Rated voltage is quoted as 240/415 V in the source data sheet — the phase-to-neutral value for a single-pole device — while the marking on the supplied unit reads 400 V~; check the marking against the installation before commissioning.
| Model | O119G |
|---|---|
| Product type | Manual transfer switch (MTS), dual-power changeover, disconnectable |
| Poles | 1P |
| Rated current | 80 A |
| Rated voltage | 240/415 V AC (source data sheet); device marking 400 V~ |
| Frequency | 50/60 Hz |
| Utilization category | AC-22A |
| Contact form | 1-0-2 |
| Insulation voltage (Ui) | 690 V |
| Electrical life | 1500 operations |
| Mechanical life | 8500 operations |
| Protection degree | IP20 |
| Ambient temperature | -5 °C to +40 °C |
| Terminal capacity | 16 mm² |
| Standards | GB/T14048.3, IEC/EN 60947-3 |
| Mounting | 35 mm DIN rail (EN 60715), fast clip device |
| Terminals | 1 and 3 at the top, 2 and 4 at the bottom |
Handle, housing and mounting
The operating handle is widened and given a deeper grip than a standard miniature breaker lever, which makes the changeover stroke easier to complete by hand and gives a clearer visual indication of the selected position. The housing is a thermoset moulding: it does not soften or drip at the temperatures a resistive or slightly inductive load can produce at the terminals, and it keeps its shape if the panel is exposed to heat.
The body is moulded from a thermosetting plastic rather than a thermoplastic. Thermosets cure into a cross-linked structure, so they do not soften, flow or drip when the terminals run hot; the housing keeps its mechanical strength and its shape at temperatures that would deform an ordinary thermoplastic enclosure. That matters at the point where the cable lug meets the terminal, which is where heat concentrates in a transfer switch used continuously at 80 A.
Installation uses the standard 35 mm rail: the device clips on with the spring-loaded foot at the bottom and is released with a screwdriver in the slot, so it can be fitted or removed without disturbing neighbouring modules. The 18 mm width keeps a changeover point inside a single module space.
Wiring
Terminal numbering follows the device: 1 and 3 at the top, 2 and 4 at the bottom. In position I terminal 1 is connected to terminal 2; in position II terminal 1 is connected to terminal 4; in the centre position the circuit is open. For dual-power changeover the manufacturer specifies feeding the normal supply and the standby supply from the lower terminals and taking the load from the upper terminals.
With the handle at I the load is fed from the normal supply; at II it is fed from the standby supply; at OFF both paths are open and the load is isolated. The incoming and outgoing side can otherwise be arranged to suit the panel, as long as the source and load are never swapped between the two changeover paths.
Dimensions
The 1P unit is 18 mm wide and 90 mm high; the depth over the handle is 72 mm and the body depth 45.5 mm, as marked A to D on the manufacturer’s drawing. Dimensions are measured by hand and are for reference — allow clearance for the handle swing and for the cable bend radius at the terminals.
Markings on the front face
The front carries the terminal numbers 1, 3 at the top and 2, 4 at the bottom, the changeover symbol beside the handle, the model and current rating, the rated voltage and frequency, the CE mark and the standard references. The specification block on the lower half repeats the utilization category AC-22A, the insulation voltage Ui 690 V and the standard numbers, so the ratings can be read with the device installed in a panel.
Typical applications
- Manual changeover between a mains supply and a standby single-phase source.
- Isolation and source selection on small distribution and control panels.
- Load transfer where a visible, lockable disconnect position is required.
- Pumping, lighting and small machine circuits that must not be fed from two sources at once.
Manufacturing
The switch is assembled and tested on the manufacturer’s own automated calibration and test lines, with the calibration stations and the moulding shop shown below.
Product reference images and drawings
Manufacturer reference views for the O119G. Check the terminal arrangement and handle positions against the supplied unit.