NewTrend · L+N switched voltage and current protector
Product overview
NewTrend PS8-13 provides true RMS voltage/current monitoring with adjustable overvoltage, undervoltage and overcurrent protection for AC 220V line-to-neutral circuits. Both L and N have disconnecting contacts, as shown in the original wiring diagrams. Select a 63A or 80A AC-1 version and factory upper- or lower-incoming wiring. The 54mm-wide DIN-rail protector displays voltage, current and fault status and automatically resets after fault recovery and the configured reset delay.
Technical selection summary
| Model | PS8-13 |
|---|---|
| Protection functions | Overvoltage, undervoltage and overcurrent |
| Measurement | True RMS voltage/current monitoring |
| Switched conductors | L and N both have disconnecting contacts |
| Isolation function | Not provided; use the upstream breaker for maintenance de-energization |
| Rated supply voltage | AC 220V (L-N) |
| Supply frequency | 45-65Hz |
| Operating voltage range | 80-400V (L-N) |
| Rated operational currents | 63A / 80A, AC-1 |
| Incoming-line versions | PS8-13U: upper incoming; PS8-13D: lower incoming |
| Power input | Maximum 3VA |
| Overvoltage setting | OFF or 230-300V |
| Undervoltage setting | 140-210V or OFF |
| Voltage-fault action delay | 0.1-10s |
| Overcurrent setting | 1A up to the ordered current rating: 63A or 80A |
| Overcurrent action delay | 2-600s |
| Power-up delay | 2-600s |
| Reset delay | 2-900s |
| Measurement error | ≤1% |
| Electrical life (AC-1) | 10,000 operations |
| Mechanical life | 1,000,000 operations |
| Operating temperature | -20 to +60°C |
| Storage temperature | -35 to +75°C |
| Mounting | DIN rail to EN/IEC 60715 |
| Protection | IP40 front panel / IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Body dimensions | 82 x 54 x 68mm |
| Weight (current catalogue) | 135g |
Operation
- Select the 63A or 80A AC-1 version and the U (upper incoming) or D (lower incoming) factory wiring configuration.
- Set overvoltage to OFF or 230-300V and undervoltage to 140-210V or OFF. Voltage-fault action delay is adjustable from 0.1-10s.
- Set the overcurrent threshold from 1A up to the selected rated current and the overcurrent delay within 2-600s. Power-up delay is 2-600s and reset delay is 2-900s.
- The original wiring diagrams show switching contacts in L and N. The front panel displays voltage and current and provides separate protection/output status indications.
- Hold M for 3s to enter settings and hold for 3s after changes to save. The decrease/power button supports manual output operation after settings and manual reset when automatic fault reset is disabled.
Typical applications
- Household-equipment circuits requiring abnormal-voltage and overcurrent protection
- DIN-rail distribution panels specifying switched L and N conductors with adjustable recovery timing
View or download PS8-13 L+N voltage/current-protector catalogue, September 2026 (PDF)
Product reference images and drawings
Original September 2026 parameters and corrected exact product photograph
Original timing, L/N wiring, dimensions and no-isolation instruction
The factory expressly states that PS8-13 has no isolation function. Disconnect the upstream circuit breaker before maintenance. Follow the exact U or D incoming-line diagram and select the overcurrent threshold within the ordered current rating; coordinate separate circuit and short-circuit protection for the installation. Installation and wiring must be performed by qualified electricians.