NewTrend · adjustable voltage protector
Product overview
NewTrend PS8-01 provides adjustable overvoltage and undervoltage protection with automatic recovery for AC 220V line-to-neutral circuits. Its single digital display shows supply voltage; this model does not provide an overcurrent protection setting. Choose a 32A, 40A, 50A, 63A or 80A AC-1 version and the factory upper- or lower-incoming wiring configuration. The 36mm DIN-rail unit has adjustable voltage-fault and reconnection delays.
Technical selection summary
| Model | PS8-01 |
|---|---|
| Protection functions | Overvoltage and undervoltage |
| Displays | Voltage |
| Rated supply voltage | AC 220V (L-N) |
| Supply frequency | 45-65Hz |
| Operating voltage range | 80-400V (L-N) |
| Rated operational currents | 32A / 40A / 50A / 63A / 80A, AC-1 |
| Incoming-line versions | U: upper incoming line; D: lower incoming line |
| Power input | Maximum 3VA |
| Overvoltage setting | OFF or 230-300V |
| Undervoltage setting | 140-210V or OFF |
| Voltage-fault action delay | 0.1-10s |
| Power-up delay (current catalogue table) | 2-600s; function diagram shows 2s setting |
| Reset delay | 2-900s |
| Measurement error | ≤1% |
| Electrical life (AC-1) | 10,000 operations |
| Mechanical life | 1,000,000 operations |
| Operating temperature | -20 to +60°C |
| Storage temperature | -35 to +75°C |
| Mounting | DIN rail to EN/IEC 60715 |
| Protection | IP40 front panel / IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Body dimensions | 82 x 36 x 68mm |
| Weight (current catalogue) | 135g |
Operation
- Select the rated-current version and the U (upper incoming) or D (lower incoming) factory wiring configuration.
- Set the overvoltage threshold within 230-300V or OFF and the undervoltage threshold within 140-210V or OFF, according to the current catalogue.
- Set the voltage-fault action delay within 0.1-10s, power-up delay within 2-600s and reset delay within 2-900s. The function diagram illustrates a 2s power-up setting.
- The single voltage display and voltage-fault indicators support supply monitoring. Overcurrent protection and current display belong to PS8-02.
Typical applications
- Household-equipment protection against abnormal supply voltage
- DIN-rail distribution panels requiring adjustable voltage thresholds and automatic reconnection
View or download PS8-01/02 adjustable voltage/current-protector catalogue (PDF)
Product reference images and drawings
Original model code, exact-model specifications and incoming-line wiring
Original protection timing diagrams, application wiring and dimensions
Follow the selected U or D incoming-line wiring. The current catalogue specifies a 2-600s adjustable power-up delay; the timing plot illustrates the 2s setting. This model provides voltage protection only; coordinate separate overcurrent and short-circuit protection for the installation. The upstream circuit breakers shown in the original application drawings are separate devices. Installation and wiring must be performed by qualified electricians.