NewTrend · Current monitoring relay
Product overview
NewTrend RI8-05A monitors AC 50Hz current through a 9mm sensing aperture. Its front potentiometer sets the threshold from 2 to 20A, and the Y1-Y2 jumper selects overcurrent or undercurrent monitoring. The 18mm DIN-rail relay uses AC/DC 24-240V and provides one SPDT output rated 10A AC-1.
Technical selection summary
| Model | RI8-05A |
|---|---|
| Function | Overcurrent or undercurrent monitoring selected by Y1-Y2 jumper |
| Monitored current | AC 50Hz |
| Current threshold range | Adjustable 2-20A |
| Measurement method | Through-hole AC current sensor |
| Sensing aperture | 9mm diameter |
| Control supply | AC/DC 24-240V, 50/60Hz or DC |
| Supply terminals | A1-A2 |
| Power input | Maximum 1.5VA |
| Supply tolerance | -15% to +10% |
| Threshold adjustment | Front potentiometer |
| Response delay | 0.1 second maximum |
| Supply indication | Green LED |
| Setting accuracy | 10% |
| Hysteresis | 5% |
| Mode jumper terminals | Y1-Y2 |
| Output contacts | 1 SPDT; 11-12-14 |
| Contact rating | 10A, AC-1 |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Output indication | Red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | DIN rail to EN/IEC 60715; 18mm module |
| Protection | IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Maximum conductor size | 1 x 2.5mm² or 2 x 1.5mm² |
| Terminal tightening torque | 0.8Nm |
| Body dimensions | 90 x 18 x 64mm |
| Overall dimensions in drawing | 95mm overall height; 82mm depth including sensor |
| Weight | 64g |
| Referenced standard | EN 60255-1 |
Operation
- Route the monitored AC conductor through the sensing aperture. The RI8-05A monitors AC 50Hz current from 2 to 20A.
- Set the threshold with the front potentiometer. Y1-Y2 open selects overcurrent monitoring; linked selects undercurrent monitoring, as shown in the current function diagram.
- Connect the control supply to A1-A2 and the SPDT output to 11-12-14. The external-current-transformer example applies to an AC measuring circuit.
Typical applications
- AC current-flow supervision in control panels
- Heating circuit and heating-cable current monitoring
- Motor and process-current supervision using a suitable external contactor
View or download RI8-05A/05B through-hole current-monitoring catalogue (PDF)
Product reference images and drawings
Original specifications and model coding
Original jumper timing, panel, wiring and complete dimensions
Use the Y1-Y2 jumper and wiring diagram in the current catalogue. The factory photograph has Y1/Y2 front terminals but B1/B2 labels in its side diagram; follow the current catalogue and the front-terminal labels. Overall depth including the sensor is 82mm. Installation and wiring must be performed by qualified electricians.