NewTrend · through-hole current monitoring relay
Product overview
NewTrend RI8-06A monitors AC 50Hz current through an isolated sensing aperture. It provides an adjustable 2-20A threshold, selectable overcurrent or undercurrent operation, memory-mode positions and separate power-up and tripping delays. The 36mm DIN-rail relay uses AC/DC 24-240V and provides two SPDT outputs rated 8A AC-1 in the current factory catalogue.
Technical selection summary
| Model | RI8-06A |
|---|---|
| Function | Overcurrent or undercurrent monitoring; selectable memory positions |
| Monitored current | AC 50Hz |
| Current threshold range | Adjustable 2-20A |
| Measurement method | Through-hole current sensor |
| Sensing aperture | 9mm diameter |
| Control supply | AC/DC 24-240V, 50/60Hz or DC |
| Supply terminals | A1-A2 |
| Power input | Maximum 1.5VA |
| Supply tolerance | -15% to +10% |
| Threshold adjustment | Front Iset potentiometer |
| Power-up delay (Tr) | 0.1-10 seconds |
| Tripping delay (Tt) | 0.1-10 seconds |
| Supply indication | Green LED |
| Setting accuracy | 10% |
| Hysteresis | 5% |
| Mode selection | Func knob; over/undercurrent and memory positions |
| Output contacts | 2 SPDT; 11-12-14 and 21-22-24 |
| Contact rating (current catalogue) | 8A, AC-1 |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Output indication | Red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | DIN rail to EN/IEC 60715; 36mm body |
| Protection | IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Maximum conductor size | 1 x 2.5mm² or 2 x 1.5mm² |
| Terminal tightening torque | 0.4Nm |
| Body dimensions | 90 x 36 x 64mm |
| Overall dimensions in drawing | 95mm overall height; 82mm depth including sensor |
| Weight (current catalogue) | 90g |
| Referenced standard | EN 60255-1 |
Operation
- Route the monitored conductor through the 9mm sensing aperture. The RI8-06A measures AC 50Hz current.
- Use the Func knob to select overcurrent or undercurrent monitoring and the required memory position. Match the selector symbols to the original timing diagram.
- Set Iset from 2 to 20A. Tr sets the power-up delay and Tt sets the tripping delay; each front dial is adjustable from 0.1 to 10 seconds.
- A1-A2 supplies the relay. The two changeover outputs use 11-12-14 and 21-22-24. The external-current-transformer example is an AC measuring arrangement.
Typical applications
- AC current-flow supervision in control panels
- Heating circuit and heating-cable current monitoring
- Motor and process-current supervision requiring two changeover outputs
View or download RI8-06A/06B through-hole current-monitoring catalogue (PDF)
Product reference images and drawings
Original specifications and model coding
Original jumper timing, panel, wiring and complete dimensions
The current factory catalogue rates the output contacts at 8A AC-1; some factory photographs carry a 10A AC-1 marking. Use the current 8A catalogue rating for selection. Follow the exact-model wiring and function diagrams for the Func selector and memory positions. Use a suitably rated contactor for the load. Installation and wiring must be performed by qualified electricians.