NewTrend · Isolated voltage monitoring relay
Product overview
NewTrend RV8-VW2 monitors an external single-phase AC or DC voltage signal through inputs separate from its AC/DC 24-240V control supply. Select V1-C for 15-150V, V2-C for 30-300V or V3-C for 60-600V. Front controls set overvoltage/undervoltage thresholds and 0.1-10 second trip and start/reset delays. Five DIP switches select the monitoring mode, latching behavior, normal-state contact logic and simultaneous or separate operation of two SPDT outputs rated 5A AC-1.
Technical selection summary
| Model | RV8-VW2 |
|---|---|
| Function | Isolated external-voltage over/under monitoring |
| Measurement | True RMS |
| Control supply terminals | A1-A2 |
| Rated control supply | AC/DC 24-240V; 50/60Hz |
| Monitoring inputs | V1, V2, V3 and common C |
| V1-C monitoring range / resistance | AC/DC 15-150V; 500kΩ |
| V2-C monitoring range / resistance | AC/DC 30-300V; 1MΩ |
| V3-C monitoring range / resistance | AC/DC 60-600V; 2MΩ |
| Input frequency | 50/60Hz AC; DC |
| Rated insulation voltage | 600V |
| Threshold setting | 10%-100% of the selected input full scale |
| Hysteresis | Single limit: adjustable 5%-20%; combined window: fixed 3% |
| Measurement error | Maximum 2% |
| Trip delay Tt | 0.1-10 seconds |
| Power-up / reset delay | 0.1-10 seconds |
| Knob-setting accuracy | 10% |
| Supply / reset indication | Green LED |
| Fault / output indication | Red LEDs |
| Output contacts | 2 SPDT; simultaneous or separate operation |
| Contact rating | 5A (AC-1) |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Mechanical life | 5,000,000 operations |
| Electrical life (AC-1) | 50,000 operations |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | 35mm DIN rail; EN/IEC 60715 |
| Protection | IP40 front panel; IP20 terminals |
| Overvoltage category / pollution degree | III / 2 |
| Maximum conductor size | Solid: 1 x 2.5mm2 or 2 x 1.5mm2; with sleeve: 1 x 2.5mm2 (AWG 12) |
| Body dimensions / weight | 90 x 36 x 70mm; 100g |
| Referenced standard | IEC 60947-5-1 |
Operation
- SW1 selects a single limit or combined over/under monitoring. In single-limit mode, SW2 chooses overvoltage or undervoltage. SW3 selects a latched trip or automatic reset.
- SW4 sets whether contacts 11-14 and 21-24 are closed or open in the normal operating state. SW5 selects simultaneous outputs or separate overvoltage/undervoltage outputs when combined monitoring is selected. Refer to the complete waveform charts.
Typical applications
- Monitoring external voltage signals separately from the control supply
- Over/under voltage supervision with selectable latching and dual-output control
Download NewTrend RV8-VW2 datasheet (PDF)
Product reference images and drawings
Separate control supply and monitoring input connections
Five DIP switches and their functions
RV8-VW2 housing dimensions; open-cover product photograph shown.
Operating waveforms: configurations 1-12
Operating waveforms: configurations 13-16
Set the threshold knobs as a percentage of the full scale for the selected V1-C, V2-C or V3-C input. Use the five DIP switches for the required monitoring and output logic. In single-limit mode, hysteresis is adjustable from 5%-20%; in combined over/under mode it is fixed at 3%. The open-cover photograph shows the DIP switches and controls. Installation and wiring must be performed by qualified electricians.