NewTrend · Digital setting timer relay
Product overview
NewTrend RT8-K2 is a digital-setting multifunction timer relay with four operating modes: on-delay, power-on interval, off-delay with a control input, and single shot. The timing range covers 0.1 seconds to 99 hours with ON and OFF settings. It has 2 SPDT contacts rated 8A AC-1 per contact, separate supply/output LEDs and an 18mm housing for 35mm DIN-rail mounting. Choose AC/DC 12-240V (W240) or AC 230V (A230) control supply.
Technical selection summary
| Model | RT8-K2 |
|---|---|
| Output contacts | 2 SPDT |
| A230 power input | AC maximum 6VA / 1.9W |
| Weight | W240: 72g; A230: 72g |
| Function | A: on-delay (power-on); B: interval (power-on); E: off-delay (S opens); F: single shot |
| Supply terminals | A1-A2 |
| Control supply options | W240: AC/DC 12-240V; A230: AC 230V; 50-60Hz |
| Supply tolerance | -15% to +10% |
| W240 burden | AC 0.09-3VA / DC 0.05-1.7W |
| Supply indication | Green LED |
| Time setting | Digital setting |
| Timing range | 0.1s-99h; ON; OFF |
| Marked time ranges | 0.1-9.9s; 1-99s; 0.1-9.9min; 1-99min; 0.1-9.9h; 1-99h; ON; OFF |
| Time setting deviation | Maximum 1% |
| Repeat accuracy | 0.2% of set value |
| Temperature coefficient | 0.05%/degree C at 20 degrees C |
| Contact rating | 2 x 8A, AC-1 |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Output indication | Red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Reset time | Maximum 200ms |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | 35mm DIN rail to EN/IEC 60715 |
| Protection | IP40 front panel; IP20 terminals |
| Operating position | Any |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum conductor size | Solid: 1 x 2.5mm2 or 2 x 1.5mm2; with sleeve: 1 x 2.5mm2 (AWG 12) |
| Terminal tightening torque | 0.4Nm |
| Body dimensions | 90 x 18 x 64mm |
| Referenced standards | EN 61812-1; IEC 60947-5-1 |
Set the required function and timing range using the selector switches, then set the time digitally. Modes E and F use the S control input and require the control supply to remain applied. Select the supply version and check the contact load rating before wiring.
Operating modes
- A – On-delay: applying the supply starts the timer. The output transfers after the selected interval and resets when the supply is removed.
- B – Power-on interval: applying the supply transfers the output immediately. It returns after the selected interval; removing the supply also resets the relay.
- E – Off-delay: keep the supply applied. Closing S energizes the output; opening S starts the delay before it releases. Closing S during the delay restarts the sequence.
- F – Single shot: with the supply applied, a trigger starts one timed output pulse. Triggers during the pulse are ignored; a new trigger can start another pulse after the output has released.
Typical applications
- Industrial equipment sequencing
- Lighting and heating-element control
- Motor and fan control circuits
Specify your enquiry
For a focused quotation, include:
- Supply version: W240 or A230
- Required function A, B, E or F and timing interval
- Load type, quantity, delivery destination and documentation requirements
Download NewTrend RT8-K2 datasheet (PDF)
Product reference images and drawings
Wiring diagram
Operating mode settings and timing charts
Timing ranges and digital setting examples
Common housing dimensions (RT8-K1 front view)
Use T to select the timing range and Fun to select mode A, B, E or F, then set the two digital counters. Modes E and F use the control input S with the supply applied continuously. ON holds the output on; OFF holds it off. Isolate power before wiring; installation must be performed by qualified electricians.