DELIXI · AC surge protective device
Product overview
The DELIXI DZ47vY reference distinguishes I+II, II and III surge-protection variants. Select the actual test class and waveform before comparing current figures, and match the pole arrangement and backup protection to the earthing system.
Technical selection summary
| Brand and series | DELIXI DZ47vY |
|---|---|
| System-voltage reference | 230 V AC phase voltage |
| I+II reference | Iimp 12.5 or 15 kA at 10/350 μs; In 25 kA |
| II reference: Imax / In, 8/20 μs | 20/10, 40/20, 65/30, 80/40, 120/60 or 160/80 kA, respectively |
| I+II / II Uc selections | 275, 385 or 440 V AC; confirm the exact version and corresponding Up |
| I+II / II pole selections | 1P, 2P, 3P, 4P, 1P+N or 3P+N according to system design |
| III reference | 1P+N; Uc 320 V; Uoc 10 kV, Isc 5 kA and Up 1.2 kV |
| Remote signalling | Optional YX on the matching variants; confirm contact and terminal requirements |
| Protection / response reference | IP20; response ≤25 ns |
| Reference standards | GB/T 18802.1; IEC 61643-11 |
Do not interpret the III variant’s 10 kV open-circuit voltage as a discharge-current rating. Use the matching table column for Up and the recommended backup device; surge-current ratings alone do not establish a suitable installation.
Typical applications
- Surge-protection branches in matched low-voltage distribution systems
- Distribution cabinets designed for the actual earthing system and prospective fault current