CHINT · Thermal overload relay
Product overview
The CHINT NR8 thermal overload relay provides overload and phase-failure protection for AC motors. Choose the manufacturer frame model and a documented adjustable current range that contains the motor nameplate current; a frame rating is not a universal current setting.
Technical selection summary
| Manufacturer models | NR8-16 / NR8-38 / NR8-100 / NR8-200 / NR8-630 |
|---|---|
| Current range selection | Select only a range allowed for the chosen frame in the controls above. The documented family spans 0.1–630 A across separate settings |
| NR8-16 settings | 0.1-0.14A, 0.14-0.2A, 0.18-0.25A, 0.22-0.32A, 0.28-0.4A, 0.35-0.5A, 0.45-0.63A, 0.55-0.8A, 0.7-1A, 0.9-1.25A, 1.1-1.6A, 1.4-2A, 1.8-2.5A, 2.2-3.2A, 2.8-4A, 3.5-5A, 4.5-6.3A, 5.5-8A, 7.5-10A, 9-13A, 12-16A |
| NR8-38 settings | 0.1-0.14A, 0.14-0.2A, 0.18-0.25A, 0.22-0.32A, 0.28-0.4A, 0.35-0.5A, 0.45-0.63A, 0.55-0.8A, 0.7-1A, 0.9-1.25A, 1.1-1.6A, 1.4-2A, 1.8-2.5A, 2.2-3.2A, 2.8-4A, 3.5-5A, 4.5-6.3A, 5.5-8A, 7.5-10A, 9-13A, 12-16A, 14-20A, 18-24A, 23-32A, 30-38A |
| NR8-100 settings | 23-32A, 30-40A, 37-50A, 48-65A, 55-70A, 63-80A, 80-93A, 80-100A |
| NR8-200 / NR8-630 settings | NR8-200: 80-160A, 100-200A; NR8-630: 125-250A, 200-400A, 315-630A |
| Protection / frequency | Three-phase bimetal; trip class 10A; temperature compensation; overload and phase failure; AC 50/60 Hz |
| Reset / mounting | 16/38/100: manual or automatic reset, plug-in contactor mounting; 200/630: manual reset, independent mounting |
| Auxiliary contacts | 1NO + 1NC, electrically separate; AC-15: 1.5 A at 380/400 V; DC-13: 0.2 A at 220 V |
| Electrical / environmental reference | Ui 690 V; −5 to +40 °C, 24-hour average ≤35 °C; altitude ≤2000 m; IEC 60947-4-1 |
Match the exact contactor and relay mounting arrangement. The overload relay does not provide short-circuit interruption; coordinate it with the specified upstream protective device and wiring. Set current from the motor and installation data, and assess restart safety before selecting automatic reset. NR8 is the thermal series; NRE8 electronic relay specifications do not apply.
Typical applications
- Overload and phase-failure protection in motor starter control assemblies
- Replacement of a matched thermal relay with the correct frame and adjustable range
Product reference images and drawings
Match the exact model, construction and supplied revision. Family reference pages can show other ratings or versions.