CHINT · Self-healing shunt capacitor
Product overview
The CHINT NWC1 self-healing shunt capacitor provides reactive-power compensation for power-factor improvement. The selected options on this page correspond to documented three-phase, 50 Hz models; voltage, kvar and phase code form the complete manufacturer designation.
Technical selection summary
| Manufacturer family | NWC1; example NWC1-0.45-40-3 = 450 V, 40 kvar, three-phase |
|---|---|
| Selected voltage / capacity | 400, 450 or 525 V; 5 / 10 / 15 / 20 / 25 / 30 / 40 kvar, three-phase -3 construction |
| Frequency scope | 50 Hz for the selected model rows; a 60 Hz or single-phase version needs its own complete row |
| Capacity tolerance | -5% to +10% |
| Permitted operation reference | Overvoltage 1.1Un for no more than 8 h per 24 h; maximum allowed current 1.3In |
| Discharge reference | The manufacturer states reduction from 2Un DC to 75 V or below within 3 minutes after disconnection |
| Harmonic limits | THDU ≤5% and THDI ≤20% in this reference; apply the installation and network study |
| Environment / standard | -25°C to +50°C, altitude up to 2000 m; IEC/EN 60831-1:2014 and 60831-2:2014 |
Size switching, protection, discharge and ventilation for the exact capacitor and network. A higher voltage nameplate does not establish a detuned-filter design or unrestricted harmonic duty. Inductor, split-phase and other constructions require their exact suffix, drawings and ratings.
Typical applications
- Power-factor correction banks
- Reactive-power compensation in low-voltage distribution
Product reference images and drawings
Match the exact model, construction and supplied revision. Family reference pages can show other ratings or versions.