Product overview
NewTrend GV2ME three-pole manual motor protection breakers. Select the exact model; thermal setting and voltage-specific short-circuit ratings follow it.
Technical selection summary
| Parameter | Specification |
|---|---|
| Supply identity | NewTrend/OEM; original-brand technical data used as supplier-authorised reference, without inherited original-brand approvals |
| Protection / operation | 3P thermal-magnetic motor protection; pushbutton ON/OFF; manually adjustable thermal current |
| Main circuit / frequency | AC up to690V;50/60Hz. No independent220V control coil is required by the manual breaker |
| Rating conditions | Selected Icu/Ics values apply atAC400/415V. Reference catalogue marks low-current rows above100kA;≥100kA is used here, not an unlimited rating |
| Other voltages | AtAC500V:ME10 50kA;ME14 10kA;ME16/20 6kA;ME21/22/32 4kA. AtAC690V:ME07 and above3kA; consult the exact reference table for service ratings and lower-current models |
| Series scope | Only exact GV2ME pushbutton/screw-terminal references are selectable. GV2P rotary and GV3ME/GV3P frames are separate enquiries; no GV2ME63 is invented |
| Accessories | Shunt,undervoltage and auxiliary blocks are optional matched accessories,not a breaker power supply. Original accessory rows retained separately |
| Installation | 35mm DIN rail or adapted screw mounting. Refer to exact outline and terminal diagram in full reference catalogue |
The old malformed0.016-0.25A range is corrected to0.16-0.25A. The series is not a contactor with a220V coil, and different-frame63A products are not mixed into the GV2ME model list.
Typical applications
- Electrical panel assembly and installation
Download complete reference catalogue (PDF)