NOARK · UL 1066 Air Circuit Breaker
Product overview
NOARK A32 and A40 UL 1066 power circuit breakers protect low-voltage distribution assemblies. A32 supports fixed or drawout construction at 800–3200A; A40 covers fixed construction at 4000A. Both families offer 3-pole and 4-pole designs with voltage-dependent Q/R/H interrupting ratings.
Technical selection summary
| Manufacturer / series | Original NOARK A32 / A40; North American UL family |
|---|---|
| Approvals / standards | UL 1066; CSA C22.2 No.268; ANSI C37.13 / C37.16 / C37.17 / C37.50, as stated in the manufacturer catalogue |
| Frame current | A32: 800, 1600, 2000, 2500, 3200A; A40: 4000A |
| Poles | 3P or 4P |
| Mounting / terminal codes | F: fixed; D: drawout; H: horizontal rear terminals; V: vertical rear terminals |
| Mounting restrictions | A32 3200A: vertical terminals only; A40 4000A: fixed mounting and vertical terminals only. |
| Rated maximum voltage | 254 / 508 / 635 / 847Vac; apply the interrupting rating at the actual voltage |
| Interrupting rating at 254/508Vac | Q: 65kA; R: 85kA; H: 100kA |
| Interrupting rating at 635Vac | Q: 65kA; R: 85kA; H: 100kA |
| Interrupting rating at 847Vac | Q: 65kA; R: 75kA; H: 85kA |
| Frequency | 50Hz / 60Hz |
| Trip protection | LI, LSI or LSIG; select the matching separately ordered trip unit and rating plug |
| Dimensions and connections | See configuration-specific manufacturer drawings below; dimension units and terminal orientation must match the selected mounting. |
Frame and trip unit together form the complete breaker. The frame code shown by the selector does not include the separately selected trip unit, rating plug, control-power accessories or final assembly bill of materials. ASD non-automatic switches shown in the shared catalogue are separate products. Breaking-class letters identify voltage-dependent ratings; do not interpret the largest kA figure as valid at every voltage.
Typical applications
- Main and feeder protection in low-voltage switchgear.
- Power distribution for data centres, industrial plants, healthcare facilities and standby-power assemblies, subject to the complete system design.