NewTrend · automatic voltage conditioner
Product overview
NewTrend Y-AVC uses an AC-DC-AC converter and a series compensation transformer to regulate load-side voltage. The AC220V L/N+PE platform is rated30kVA and135A. The AC380V three-phase four-wire+PE platform covers catalogue ranges of30–500kVA and45–750A, with exact capacity configured for the application. Standard compensation is±20% of nominal voltage; the wider-40% to+30% compensation range is described as customization.
Technical selection summary
| Model | Y-AVC |
|---|---|
| AC220V platform | 30kVA;135A;L/N+PE |
| AC380V platform | 30–500kVA;45–750A;three-phase four-wire+PE;exact rating project-configured |
| Function | Voltage compensation |
| Input voltage range | -40% to+30%, catalogue value |
| Standard compensation range | Nominal AC220V or AC380V ±20%;-40% to+30% compensation is customization |
| Output voltage accuracy | ±1% |
| Compensation response | <20ms |
| Output voltage THD increment | ≤1%;increment, not total output THD |
| Rated / allowable frequency | 50/60Hz;45–63Hz |
| AC overload capability | 1.1× continuous |
| Converter / transformer ratio | 5:1 |
| Transformer capacity | 220V platform:6kVA;380V platform:6–100kVA |
| Transformer construction | Dry-type, laminated silicon-steel core;frame and enclosure grounded |
| Transformer insulation | Class H |
| Transformer turns ratio, catalogue | 220:44 |
| Transformer overload | 1.1× continuous |
| Transformer temperature rise | ≤90K |
| Transformer standard listed in catalogue | IEC726; catalogue declaration |
| Fault records | Records for30 fault days, unlimited entries within storage range |
| Protection functions | Overload, software/hardware overcurrent, grid over-/undervoltage, overtemperature and abnormal frequency protection |
| Protection rating | IP20;IP54 customization described separately |
| Noise | ≤70dB |
| Ambient temperature | -10 to+50°C;derating above40°C |
| Relative humidity | ≤90%,no condensation at monthly minimum25°C |
| Altitude | <2000m;above2000m derate perGB/T3859.2 |
| Pollution degree | ≤ClassIII |
| Cabinet installation | Cabinet-type;exact outline not specified in this catalogue page |
Operation
- The converter regulates the magnitude and polarity of voltage applied through a compensation transformer connected in series with the main circuit.
- Voltage is controlled continuously and by phase. The circuit includes a breaker, contactor and bypass switching for the stated maintenance arrangement.
- The input voltage envelope and standard compensation range are separate catalogue values. Confirm required capacity and voltage-event depth and duration for the application.
Typical applications
- Industrial loads requiring stable supply voltage
- Facilities exposed to voltage deviation or phase-unbalanced loading
- Applications requiring electronic voltage compensation with a maintenance bypass arrangement
View or download Y-AVC original catalogue, September 2026 (PDF)
Product reference images and drawings
Original AVC electrical, transformer and environmental parameters
Original AVC ordering-code guide
Original AVC compensation-transformer circuit
The photograph is the original AVC cabinet-family example. The ordering-code guide illustrates three-phase4L coding and lists selected example capacities; the latest technical table separately specifies the220V single-phase30kVA platform and the380V30–500kVA range. Exact three-phase capacity, current and cabinet arrangement are confirmed for the project. Installation and wiring must be performed by qualified electricians.