NewTrend · adjustable overcurrent protection
Product overview
The OVPD1-II is a DIN-rail current protector for 230V AC circuits up to 63A. It displays current and disconnects the load when the adjustable overcurrent threshold is exceeded for the selected action delay. Automatic recovery and programmable startup and recovery delays support controlled restarting.
Technical selection summary
| Model | OVPD1-II |
|---|---|
| Supply voltage | 230V AC, 50/60Hz |
| Maximum load current | 63A |
| Overcurrent setting | 1–63A; default 40A |
| Overcurrent action delay | 0.1–30s; default 0.5s |
| Recovery delay | 1–500s; default 30s |
| Power-on delay | 1–500s; default 10s |
| Repeated fault limit | 1–20 or OFF; manual reset after reaching the selected limit |
| Display and controls | Current LED display, SET and up/down buttons, manual ON/OFF switch |
| Power consumption | Less than 2W |
| Rated insulation voltage | 400V |
| Protection degree | IP20 |
| Installation | 35mm DIN rail |
| Dimensions | 81 × 36 × 70mm; drawing dimensions are approximate |
Adjustment and operation
Use the SET and up/down keys to set the power-on delay, current threshold, overcurrent recovery delay, action delay and repeated-fault limit. The red switch provides a manual ON/OFF control. The display also supports current calibration. Select the threshold and external circuit protection to suit the conductors and connected load.
Recovery and repeated faults
The device can reconnect after the configured recovery delay. When repeated protection operations reach the selected limit, press the up and down keys together for more than three seconds to reset manually. The limit can also be disabled using the OFF setting.
Dimensions and installation
The moulded housing clips to a 35mm DIN rail. The drawing identifies an approximate 81mm height, 36mm width and 70mm overall depth. The input and output terminals are marked L and N; isolate the circuit before wiring or servicing.
Typical applications
Current monitoring and adjustable overcurrent disconnection for compatible single-phase loads in distribution panels, including equipment and motor circuits within the device rating.