NewTrend · DIN-rail switching power supplies
Product overview
The MDR and EDR power supplies convert a 100–240V AC supply to a single regulated DC output for control equipment. This page offers three configurations: MDR-20-24 at 24V/1A, MDR-60-24 at 24V/2.5A and EDR-75-12 at 12V/6.3A. The compact MDR units use a ventilated plastic enclosure, while the taller EDR unit uses a metal enclosure.
Technical selection summary
| MDR-20-24 | 24V DC / 1A; 24W output capacity; plastic housing |
|---|---|
| MDR-60-24 | 24V DC / 2.5A; 60W output capacity; plastic housing |
| EDR-75-12 | 12V DC / 6.3A; 75.6W output capacity; metal housing |
| AC input | 100–240V AC, 50/60Hz |
| Input nameplate current | MDR-20-24:0.55A; MDR-60-24:1.3A; EDR-75-12:1.6A |
| Output adjustment | Front +V ADJ control, approximately ±10% |
| Protection functions | Short circuit, overload, overvoltage and overcurrent |
| Cooling | Free-air convection; keep ventilation openings clear |
| Mounting | 35mm DIN rail |
| MDR-20 dimensions | 22mm wide × 90mm high × 100mm deep |
| MDR-60 dimensions | 38mm wide × 88mm high × 100mm deep |
| EDR-75 dimensions | 31mm wide × 125mm high × 112mm deep |
| Working temperature | MDR:−20°C to +70°C; EDR illustrated installation:maximum surrounding air temperature 50°C |
| Storage temperature | −40°C to +85°C |
| Humidity | 0–95% RH, non-condensing |
| Terminals | PE / N / L input; +V / −V output; MDR versions also show DC OK terminals |
DC output and adjustment
Select the complete model for the required output voltage and current. The front +V ADJ control trims the output voltage, and the DC OK indicator provides a local status check. Keep the connected load within the selected model’s output rating. Cooling is by natural convection, with no external cooling fan shown.
MDR-20-24 connections
The lower terminals are protective earth, neutral and line. The upper terminals identify the positive and negative DC output and the separate DC OK connection. Follow the markings when connecting the control circuit.
MDR-60-24 connections
The larger MDR version provides paired positive and negative output terminals and a separate pair marked DC OK. Its input remains PE, N and L. The front panel identifies a 24V DC,2.5A output and a 100–240V AC input.
EDR-75-12 connections and installation
The EDR version places the negative and positive DC output terminals above the front panel and the PE, N and L input below it. Use copper conductors rated for at least 75°C. The illustrated unit specifies a maximum surrounding air temperature of 50°C and installation in a pollution-degree 2 environment. Isolate the input supply before installation or servicing.
Protection and ventilation
The power supplies include short-circuit, overload, overvoltage and overcurrent protection. Keep the housing vents clear, install inside a suitable dry electrical enclosure and allow sufficient air circulation. These open-terminal units are not waterproof and should not be installed in wet locations.
MDR-20 dimensions
The narrow MDR-20 enclosure is 22mm wide,90mm high and 100mm deep.
MDR-60 dimensions
The MDR-60 enclosure is 38mm wide,88mm high and 100mm deep. Its rear mounting clip engages a standard DIN rail.
EDR-75 dimensions
The EDR-75 enclosure is 31mm wide,125mm high and 112mm deep. Allow additional clearance for the upper output wiring and lower AC input wiring.
Typical applications
For DC control power in automation panels, instrumentation, communications equipment and lighting-control installations. Select the model to match the DC voltage and continuous load of the connected equipment.