NewTrend / OEM · EOCR-3DE/3EZ
Product overview
NewTrend/OEM EOCR-3DE and EOCR-3EZ monitor three-phase motor current through integral current transformers. The 3DE includes a load-alert output; the 3EZ version adds ground-fault protection.
Technical selection summary
| Direct current range | 0.5–60A with one conductor pass; 0.25–30A with two passes; 0.1–12A with five passes, per original CT table |
|---|---|
| External CT | 1–960A overall through exact 10:5 to 800:5 CT rows. Select the matching CT ratio and range from the retained native table; an external CT is not assumed included |
| Control supply | 24VAC/DC, 110VAC ±15%, or 220VAC ±15%; AC 50/60Hz |
| Outputs | 3DE: OL 1NO+1NC and AL 1NO. 3EZ: OL 1NO and GR 1NO. Contact rating 3A at 250VAC resistive |
| Protection | Overcurrent, undercurrent, phase loss, unbalance, reversal and locked rotor; ground fault only on 3EZ |
| Timing | D-TIME 1–200s; inverse O-TIME 1–30; definite O-TIME 0.2–30s, as labelled in the original reference |
| Installation / wiring | 35mm DIN rail; retain separate 3DE and 3EZ wiring diagrams. This OEM product is not represented as original Samwha/Schneider |
Provide motor current, supply, selected version, CT ratio if required and quantity. Confirm the exact delivered suffix and wiring before installation.
Typical applications
- Motor overcurrent and phase-fault monitoring
- Ground-fault monitoring using the matched 3EZ sensing arrangement
Specify your enquiry
For a focused quotation, include:
- Version: 3DE, 3EZ A, 3EZ B
- Control Voltage: AC/DC24V, AC110V, AC220V
- Ground Fault Range: None, 0.02–3A, 0.2–10A
- Contacts: OL:1NO+1NC; AL:1NO, OL:1NO; GR:1NO
- Required quantity, load and exact installation.