DELIXI ELECTRIC · CDR6i
Product overview
DELIXI CDR6i provides motor overload and phase-failure protection. Choose the current-setting range first, then the matching frame where more than one is listed.
Technical selection summary
| Frame / range scope | 25, 38, 93, 185, 630; only the listed frame/current-range pairs |
|---|---|
| Trip class by frame | 25/38:10A; 93/185:10; 630:10A |
| Main insulation rating | Ui690V; not an automatically assigned motor operating voltage |
| Functions | Overload, phase failure, manual/automatic reset, stop, test and trip indication |
| Contactor matching | Follow the exactCDC6i row for the selected frame/range in the attached catalogue |
| Mounting | 25/38/93/185:matched direct or independent assembly as specified; 630:independentF construction |
| Load protection boundary | Separate short-circuit protection is required; use the listed fuse/contactor coordination |
| Auxiliary circuit | 1NO+1NC; use the frame-specific AC-15/DC-13 ratings, not main motor current |
The setting range is a physical relay variant; the setting knob and reset mode are operating adjustments. Frame, trip class, contactor interface and mounting must correspond to the exact manufacturer row. A thermal overload relay is not a standalone short-circuit breaker.
Typical applications
- Motor overload and phase-failure control circuits.
Product reference images and drawings