CNC Electric · YCT8-M2
Product overview
The CNC Electric YCT8-M2/A230 is a multifunction DIN-rail time relay with ten selectable functions and two changeover contacts. The original photographed unit is marked AC230V, 50/60Hz. Its two AC-1 outputs are each rated 16A; the setting range is 0.1 seconds to 10 days.
Technical selection summary
| Complete manufacturer ordering model | YCT8-M2/A230: M = multifunction; 2 = two SPDT contacts; A230 = AC230V supply |
|---|---|
| Control supply / tolerance | AC230V, 50/60Hz / −15% to +10% |
| Supply power input | AC maximum 6VA / 1.9W, A230 two-contact version |
| Output contacts | 2 × SPDT (2CO): 15/16/18 and 25/26/28; 15 and 25 common |
| Rated output current / load category | 2 × 16A, AC-1 resistive load; not a motor-load rating |
| Switching voltage / minimum DC breaking power | 250V AC / 24V DC; 500mW minimum DC breaking power |
| Functions | 10 selectable functions A–J: five supply-controlled timing functions, four control-input timing functions and one latching-relay function |
| Time range / setting | 0.1s to 10 days in ten ranges, plus ON/OFF positions; rotary potentiometer setting |
| Time deviation / repeat accuracy | 10% mechanical setting / 0.2% set-value stability |
| Temperature coefficient | 0.05% per °C at 20°C |
| Supply and control terminals | A1–A2 supply; S control input; follow the original M2 diagram |
| Indicators | Green supply LED; red output LED |
| Reset time | Maximum 200ms |
| Mechanical / electrical life | 10,000,000 / 100,000 operations (electrical life under AC-1 conditions) |
| Operating / storage temperature | −20°C to +55°C / −35°C to +75°C |
| Protection degree | IP40 front panel / IP20 terminals |
| Overvoltage category / pollution degree | III / 2 |
| Conductor capacity / tightening torque | Solid: 1 × 2.5mm² or 2 × 1.5mm²; sleeved: 1 × 2.5mm² / 0.4N·m, original instructions |
| Dimensions / mounting | 90 × 18 × 64mm / EN/IEC 60715 DIN rail; one module |
| Standards | EN 61812-1; IEC 60947-5-1 |
Selection and installation
This page covers the M2 two-contact AC230V version. Use the original M2 wiring diagram, including 15/16/18 and 25/26/28. The two outputs follow the selected timing function; they are not two independent timers. Use appropriate contactors for motor loads and follow the original A–J function diagrams. Isolate the supply before changing wiring.
Typical applications
Timed control of lighting, heating, pumps, fans and automation circuits requiring two synchronized changeover contacts.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.
Download the complete original CNC YCT8-M2 catalogue (PDF)
Download the complete original CNC YCT8-M2 instructions (PDF)