CHINT · Online motor soft starter
Product overview
This CHINT NJR5-ZX4 listing concerns online soft starting and soft stopping of three-phase squirrel-cage AC motors on a 460 V main supply. Select the full NJR5 current code from the matching voltage-specific manufacturer row, together with the motor and load duty.
Technical selection summary
| Listing / voltage code | NJR5-…/ZX4; ZX4: AC 460 V |
|---|---|
| Main-circuit input range | AC 414–504 V in the manufacturer technical table |
| Power scope on this page | 9–315 kW; matched model/current rows are shown in the technical reference table |
| Model code versus current | Use the separate rated-current column. The numeric model code is not necessarily the actual continuous current |
| Start / stop reference | Soft start 2–60 s and soft stop 2–60 s; choose the mode and settings for the load |
| Communication / control | RS485 with Modbus; confirm controller revision, control supply and terminal diagram |
| Installation conditions | Normal operation −10°C to +40°C; apply manufacturer temperature and altitude derating and cabinet ventilation requirements |
| Manufacturer standard reference | IEC 60947-4-2; exact-unit approvals require the applicable document |
The ZX4 voltage suffix cannot be exchanged for another voltage code. Use the full current-code row at 460 V; a power figure alone does not select the starter. The series overview mentions a 1000 code while selection rows give actual currents up to 900 A: use the marked rated current, not a family headline. Only combinations tied to the voltage-specific manufacturer rows are covered here. Match starting frequency, duty, external isolation/short-circuit protection and the actual controller/terminal diagram. Online starting is not a general variable-speed-drive function.
Typical applications
- Pump and fan motor starting with the matching load settings
- Compressor and machinery starting within documented motor duty
Voltage-specific technical reference
Use the exact manufacturer model and rated-current column at the stated main voltage. The following rows cover the power scope of this listing; motor/load and installation conditions still apply.
| Manufacturer model | Rated current (A) | Motor power (kW) |
|---|---|---|
| NJR5-15/ZX4 | 15 | 9 |
| NJR5-22/ZX4 | 22 | 15 |
| NJR5-30/ZX4 | 29 | 18.5 |
| NJR5-37/ZX4 | 36 | 22 |
| NJR5-44/ZX4 | 42 | 30 |
| NJR5-60/ZX4 | 57 | 37 |
| NJR5-74/ZX4 | 70 | 45 |
| NJR5-90/ZX4 | 84 | 55 |
| NJR5-110/ZX4 | 103 | 75 |
| NJR5-150/ZX4 | 140 | 90 |
| NJR5-180/ZX4 | 167 | 110 |
| NJR5-220/ZX4 | 207 | 132 |
| NJR5-264/ZX4 | 248 | 150 |
| NJR5-320/ZX4 | 300 | 185 |
| NJR5-370/ZX4 | 349 | 220 |
| NJR5-440/ZX4 | 404 | 250 |
| NJR5-500/ZX4 | 459 | 280 |
| NJR5-560/ZX4 | 514 | 315 |
Product reference images and drawings