CHINT · NC1 4-Pole DC-Coil Contactor, 25–40 A
Product overview
CHINT NC1-2504Z and NC1-4004Z are four-normally-open-pole contactors for AC power circuits with DC-operated coils. Select a complete manufacturer reference; DC coil supply does not make this a DC load-switching contactor.
Technical selection summary
| Main poles | 4NO; 04 contact arrangement |
|---|---|
| AC-3 Ie at 380/400 V | NC1-2504Z: 25 A; NC1-4004Z: 40 A |
| AC-1 / Ith | 45 A and 60 A respectively |
| DC coil options | 25 A: 24, 48, 110, 125, 220 V; 40 A: 24, 48, 110, 220 V |
The catalogue ordering rows list each actual DC-coil reference. The 125 V option is listed for NC1-2504Z only; do not apply it to NC1-4004Z.
Typical applications
- CHINT NC1-2504Z and NC1-4004Z are four-normally-open-pole contactors for AC power circuits with DC-operated coils.
Product reference images and drawings