CHINT · Electronic Molded Case Circuit Breaker
Product overview
CHINT 271335 is a 3-pole, 250 A MCCB for industrial AC distribution. The EN electronic trip unit provides adjustable overload and short-circuit protection.
Model and trip unit
NM8N-250S-EN-250/3/22 identifies the 250 A frame, S breaking-capacity class, EN electronic release and 3-pole Frame 22 configuration. Long-time pickup Ir is adjustable from 0.4 to 1.0 × In, equivalent to 100–250 A for this code.
Technical selection summary
| Ordering code | 271335 |
|---|---|
| Manufacturer model | NM8N-250S-EN-250/3/22 |
| Frame | NM8N-250 / Frame 22 |
| Poles | 3P |
| Rated current (In) | 250 A |
| Trip unit | EN basic electronic release |
| Thermal adjustment (Ir) | 0.4–1.0 × In (100–250 A) |
| Rated voltage | 380/415 V AC |
| Maximum operating voltage | 690 V AC |
| Icu | 50 kA at 380/400/415 V AC |
| Ics | 50 kA at 380/400/415 V AC |
| Ui | 1000 V |
| Uimp | 8 kV |
| Power dissipation | 75 W |
| Utilization category | B |
| Ingress protection | IP00 / IP40 with terminal covers |
| Dimensions (H × W × D) | 157 × 105 × 88.7 mm |
| Standard | EN 60947-2 |
| EAN | 6941716422363 |
| ETIM | EC000228 |
| Units per pack | 1 |
| Units per carton | 8 |
Short-circuit ratings by voltage
| Operating voltage | Icu | Ics |
|---|---|---|
| 380 / 400 / 415 V AC | 50 kA | 50 kA |
| 440 V AC | 50 kA | 50 kA |
| 500 V AC | 40 kA | 40 kA |
| 660 / 690 V AC | 8 kA | 8 kA |
Typical applications
- Industrial distribution panels and power centers
- AC feeder circuits requiring adjustable protection
Download CHINT NM8N series catalogue (PDF)