CHINT · Molded Case Circuit Breaker
Product overview
CHINT 269306 is a 4-pole thermal-magnetic molded case circuit breaker for industrial AC distribution. The 630 A frame contains a 400 A release for overload and short-circuit protection.
Model and trip unit
NM8N-630R-400/4/23 identifies the 630 A frame, R breaking-capacity class, 400 A rated current and 4-pole Frame 23 configuration. The thermal adjustment for this code is 0.7 – 1 x In.
Technical selection summary
| Ordering code | 269306 |
|---|---|
| Manufacturer model | NM8N-630R-400/4/23 |
| Standard | EN 60947-2 |
| Poles | 4P |
| Rated current (In) | 400 A |
| Rated voltage | 380/415 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Impulse withstand voltage (Uimp) | 8 kV |
| Maximum operating voltage | 690 V AC |
| Ultimate breaking capacity (Icu) | 150 kA (AC380/400/415V) |
| Service breaking capacity (Ics) | 150 kA (AC380/400/415V) |
| Power dissipation | 96 W |
| Degree of protection | IP00 / IP40 with terminal covers |
| Dimensions (H × W × D) | 255x185x113 mm |
| Thermal adjustment (Ir) | 0.7 – 1 x In |
| Utilization category | A |
| Trip unit | Thermal-magnetic |
| Frame designation | Frame 23 |
| Units per pack | 1 |
| Units per carton | 2 |
| EAN | 6941716427504 |
| ETIM | EC000228 |
Short-circuit ratings by voltage
| Operating voltage | Icu | Ics |
|---|---|---|
| 380 / 400 / 415 V AC | 150 kA | 150 kA |
| 440 V AC | 100 kA | 100 kA |
| 500 V AC | 50 kA | 50 kA |
| 660 / 690 V AC | 15 kA | 15 kA |
Typical applications
- Industrial power distribution panels and power centers
- Feeder protection in motor control centers
Download CHINT NM8N series catalogue (PDF)
Product reference images and drawings
The following catalogue pages cover the NM8N family. See the specification table above for the exact ordering code.