CHINT · Online motor soft starter
Product overview
This CHINT NJR5-ZX3 listing concerns online soft starting and soft stopping of three-phase squirrel-cage AC motors on a 380 V main supply. Select the full NJR5 current code from the matching voltage-specific manufacturer row, together with the motor and load duty.
Technical selection summary
| Listing / voltage code | NJR5-…/ZX3; ZX3: AC 380 V |
|---|---|
| Main-circuit input range | AC 323–437 V in the manufacturer technical table |
| Power scope on this page | 45, 90, 220 kW; matched model/current rows are shown in the technical reference table |
| Model code versus current | Use the separate rated-current column. The numeric model code is not necessarily the actual continuous current |
| Start / stop reference | Soft start 2–60 s and soft stop 2–60 s; choose the mode and settings for the load |
| Communication / control | RS485 with Modbus; confirm controller revision, control supply and terminal diagram |
| Installation conditions | Normal operation −10°C to +40°C; apply manufacturer temperature and altitude derating and cabinet ventilation requirements |
| Manufacturer standard reference | IEC 60947-4-2; exact-unit approvals require the applicable document |
The ZX3 voltage suffix cannot be exchanged for another voltage code. Use the full current-code row at 380 V; a power figure alone does not select the starter. The series overview mentions a 1000 code while selection rows give actual currents up to 900 A: use the marked rated current, not a family headline. Only combinations tied to the voltage-specific manufacturer rows are covered here. Match starting frequency, duty, external isolation/short-circuit protection and the actual controller/terminal diagram. Online starting is not a general variable-speed-drive function.
Typical applications
- Pump and fan motor starting with the matching load settings
- Compressor and machinery starting within documented motor duty
Voltage-specific technical reference
Use the exact manufacturer model and rated-current column at the stated main voltage. The following rows cover the power scope of this listing; motor/load and installation conditions still apply.
| Manufacturer model | Rated current (A) | Motor power (kW) |
|---|---|---|
| NJR5-90/ZX3 | 84 | 45 |
| NJR5-180/ZX3 | 167 | 90 |
| NJR5-440/ZX3 | 404 | 220 |
Product reference images and drawings
Match the exact current frame, voltage suffix, contact/pole construction and connection dimensions. Family images may show other versions; use the applicable manufacturer row and drawing for the ordered unit.