NewTrend · Battery Energy Storage Systems
Product overview
YHV-261SLC is an all-in-one 125kW / 261.248kWh commercial and industrial energy storage system. The cabinet integrates batteries, BMS, PCS, fire protection, liquid-cooling units and energy management. Its prefabricated modular construction supports transportation, installation, maintenance and multi-level parallel connection.
Key features
- 314Ah LFP cells; 1P260S battery grouping formed by five 1P52S packs.
- 832V nominal battery voltage, 728–936V operating range and 150A rated charge/discharge current.
- 125kW AC power; AC380–415V, 180A, 50/60Hz; 3P+N+PE, non-isolated connection.
- System energy efficiency ≥92%; grid-tied and off-grid operating modes.
- Intelligent liquid cooling, graded isolation/interlocking protection and multi-level fire protection.
- IP55, C3 corrosion protection, aerosol fire protection and noise ≤65dB.
- EMS equipment control, remote monitoring, intelligent operation and maintenance.
- Peak shaving, load shifting, capacity expansion, backup reserve, grid balancing and capacity management.
Technical selection summary
| AC Parameters | |
| Rated Power | 125kW |
| Rated Voltage | AC380V to 415V |
| Rated Current | 180A |
| Rated Frequency | 50Hz/60Hz |
| Isolation Method | Non-isolated |
| DC Parameters | |
| Battery Type | 314Ah, LFP Battery |
| Battery Rated Capacity | 261kWh |
| Battery Rated Voltage | 832V |
| Battery Voltage Range | 728V ~ 936V |
| Rated Charge/Discharge Current | 150A |
| Cycle Life | ≥8000 cycles (at 25°C, 0.5C, 80% DOD) |
| System Parameters | |
| System Energy Efficiency | ≥92% |
| Operating Modes | Grid-Tied/ Off-Grid |
| Communication Method | CAN, 485, TCP/IP |
| Protection Level | IP55 |
| Anti-Corrosion Level | C3 |
| Fire Protection | Aerosol |
| Operating Temperature | -29°C to +50°C |
| Operating Humidity | 0% to 95% (no condensation) |
| Altitude | ≤2000m (derating above 2000m) |
| Cooling Method | Intelligent Liquid Cooling |
| Overall Dimensions (WHD) | 1110mm*2350mm*1690mm |
| Weight | Approximately 2.6 tons |
The installation environment must be dry, well ventilated and free from corrosive substances and electromagnetic interference. Operate between −29°C and +50°C, maintain heat-dissipation clearances, install on a stable surface and provide reliable grounding. Inspect connections, cable condition and insulation; service batteries and clean vents regularly without allowing cleaning fluid into equipment. Do not place flammable/explosive materials on the cabinet or make unauthorized modifications. Supplied certification, commissioning, service and commercial warranty terms are To be confirmed.
Standards, conformity and fire-suppression references describe the documented source design. Supplied certification, regional approvals, project-level compatibility and OEM warranty applicability are To be confirmed.
System applications
Industrial parks, commercial buildings, EV charging stations, communication facilities, data centers, wind/solar microgrids, grid-frequency support and distributed energy-storage projects. System engineering must match local grid, fire-protection and installation requirements.