NewTrend · Photovoltaic DC Circuit Protection
Product overview
D-125 and D-250 are non-polar, four-pole PV DC moulded-case circuit breakers for overload and short-circuit protection, overcurrent control and infrequent operation. The 1000 V DC family covers 63–250 A, with separate 125 A and 250 A frame choices. Applications include solar PV DC distribution, inverter circuits, EV charging stations, commercial battery storage and UPS systems.
Key features
- IEC60947-2 / GB14048.2 reference, selectivity category A.
- 1000 V DC, four poles; 20 kA ultimate and 15 kA service breaking capacity.
- Thermal-magnetic tripping, non-polar construction and grounded or ungrounded system application with the correct documented wiring.
- 14000 mechanical and 2000 electrical operations.
- IP40 enclosure sides and IP20 connection terminals.
- Terminal end covers and interphase barriers; optional operating and signalling accessories.
- Original product-page extreme-ambient test reference: −40 °C to +85 °C. Continuous operating-current derating across that range: To be confirmed.
Frame and current selection
| Parameter | D-125 | D-250 |
|---|---|---|
| Maximum frame current | 125 A | 250 A |
| Selectable rated currents | 63 / 80 / 100 / 125 A | 125 / 160 / 200 / 250 A |
| Poles | 4P | 4P |
| Operational voltage (Ue) | 1000 V DC | 1000 V DC |
| Ultimate breaking capacity (Icu) | 20 kA | 20 kA |
| Service breaking capacity (Ics) | 15 kA | 15 kA |
| Conductor cross-section | 16–50 mm² | 50–120 mm² |
| Case size table, L × W × H | 150.5 × 122 × 92.5 mm | 165 × 140 × 88 mm |
The current factory-page photographs show the D-250 family from three angles. D-125 uses the explicitly labelled photograph from the same directly linked technical document. The complete model drawings distinguish the body, fixing centres and operator-inclusive dimensions; use those drawings for installation.
Common electrical characteristics
| Standard | IEC60947-2 / GB14048.2 |
|---|---|
| Selectivity category | A |
| Insulation voltage (Ui) | 1000 V DC |
| Impulse withstand voltage (Uimp) | 8 kV |
| One-minute power-frequency withstand voltage | 3.8 kV |
| Tripping system | Thermal magnetic |
| Mechanical endurance | 14000 cycles |
| Electrical endurance | 2000 cycles |
| Polarity | Non-polar |
| Side protection | IP40 |
| Connection terminals | IP20 |
| Storage temperature | −40 °C to +85 °C |
| Direct rotary handle, RHD | Optional |
| Extended rotary handle, ERH | Optional |
| MOD operating mode | Optional; exact supplied accessory applicability: To be confirmed |
| Shunt release, SHT | Optional; coil specification and compatibility: To be confirmed |
| Auxiliary release/contact | Optional; compatibility: To be confirmed |
| Terminal end cover | Yes in the document configuration |
| Interphase barriers | Yes in the document configuration |
| Factory warranty reference | Five years / free replacement, as stated on the source page; supplied-product warranty terms: To be confirmed |
| Factory certification references | CCC / TUV, CE and CB; applicability and markings of the supplied product: To be confirmed |
D-250 4D wiring resistance and power loss
| Rated current | 125 A | 160 A | 200 A | 250 A |
|---|---|---|---|---|
| Resistance | 0.025 mΩ | 0.020 mΩ | 0.015 mΩ | 0.011 mΩ |
| I²R power loss | 0.39 W | 0.51 W | 0.60 W | 0.69 W |
Characteristic curves and wiring references
The complete document retains the time/current characteristic curve with minimum and maximum bounds, peak let-through current curve, thermal-stress curve and all 4A, 4B, 4C, 4D and 4S contact wiring diagrams. These are external circuit references, not interchangeable voltage approvals. Follow the diagram applicable to the exact DC system.
| D-250/4P test reference | 5 kA | 10 kA | 15 kA | 20 kA |
|---|---|---|---|---|
| Peak current, Ip | 4.5 kA | 6.5 kA | 7.8 kA | 8.5 kA |
| Thermal stress, I²t | 195 kA²s | 352 kA²s | 472 kA²s | 544 kA²s |
Test condition: Ue = 1000 V, In = 250 A, T = 10 ms. These curve-test points are distinct from the breaker’s selected 20 kA Icu rating.
Accessory and installation references
The directly linked document illustrates a left-mounted auxiliary contact synchronized with the main contacts and a right-mounted shunt release for D-250, with IEC/EN62019 references. CDM3-250 and CM3-250 are retained as the document’s accessory reference codes. Exact accessory selection, supplied coil rating and model compatibility: To be confirmed; these accessory codes are not selectable as verified supplied options.
| Auxiliary contact reference | CDM3-250; 1 changeover contact (CO), auxiliary function |
|---|---|
| Auxiliary contact ratings | AC13: 3 A at 250 V; AC15: 2 A at 250 V; DC12: 0.5 A at 110 V |
| Auxiliary minimum operating current | 10 mA per contact |
| Auxiliary minimum operating voltage | 11 V DC per contact |
| Auxiliary frequency | 50 / 60 Hz |
| Shunt release reference | CM3-250; exact coil/voltage applicability: To be confirmed |
| Shunt table reference values | AC: 2 A at 220/415 V; AC: 1 A at 24/48 V; DC: 1 A at 24/48 V; min. voltage 8.4 V, max. voltage 26.4 V; min. current 1 A, max. current 2 A; 50/60 Hz. Applicability of these printed values to a supplied coil: To be confirmed |
| Shunt table contact/function fields | To be confirmed; complete original reference table retained in the PDF |
Complete technical document
Download the complete three-page D-125 / D-250 family datasheet
The complete original layout retains all rating groups, curves, test points, wiring alternatives, dimension drawings and accessory references.