NewTrend · united-structure metric nylon cable gland
Product overview
NewTrend united-structure metric nylon cable glands provide cable-entry clamping and sealing in electrical enclosures. The 42 exact B/BS/BSL/BL items cover M8–M63 threads, cable outside-diameter ranges from 1–2.5mm to 32–44mm, and model-specific thread lengths. Select an exact item and black or grey. M8 uses 1.25mm pitch; the other listed metric threads use 1.5mm pitch. The original photograph is a grey family illustration.
Technical selection summary
| 8B-4.5 | Thread M8×1.25; cable OD 2.5-4.5mm; C1 thread OD 8mm; C2 thread length 7.5mm; spanner A/CF 13/12mm |
|---|---|
| 8B-2.5 | Thread M8×1.25; cable OD 1-2.5mm; C1 thread OD 8mm; C2 thread length 7.5mm; spanner A/CF 13/12mm |
| 10B-6 | Thread M10×1.5; cable OD 2-6mm; C1 thread OD 10mm; C2 thread length 8mm; spanner A/CF 15/13mm |
| 10B-3 | Thread M10×1.5; cable OD 1.5-3mm; C1 thread OD 10mm; C2 thread length 8mm; spanner A/CF 15/13mm |
| 12BS-6.5 | Thread M12×1.5; cable OD 3-6.5mm; C1 thread OD 12mm; C2 thread length 8mm; spanner A/CF 17/16mm |
| 12BS-5.5 | Thread M12×1.5; cable OD 3-5.5mm; C1 thread OD 12mm; C2 thread length 8mm; spanner A/CF 17/16mm |
| 12BSL-6.5 | Thread M12×1.5; cable OD 3-6.5mm; C1 thread OD 12mm; C2 thread length 15mm; spanner A/CF 17/16mm |
| 12BSL-5.5 | Thread M12×1.5; cable OD 3-5.5mm; C1 thread OD 12mm; C2 thread length 15mm; spanner A/CF 17/16mm |
| 12B-8 | Thread M12×1.5; cable OD 4-8mm; C1 thread OD 12mm; C2 thread length 9mm; spanner A/CF 17/19mm |
| 12B-5.5 | Thread M12×1.5; cable OD 3-5.5mm; C1 thread OD 12mm; C2 thread length 9mm; spanner A/CF 17/19mm |
| 16BS-8 | Thread M16×1.5; cable OD 4-8mm; C1 thread OD 16mm; C2 thread length 9mm; spanner A/CF 22/19mm |
| 16BS-5.5 | Thread M16×1.5; cable OD 3-5.5mm; C1 thread OD 16mm; C2 thread length 9mm; spanner A/CF 22/19mm |
| 16BSL-8 | Thread M16×1.5; cable OD 4-8mm; C1 thread OD 16mm; C2 thread length 15mm; spanner A/CF 22/19mm |
| 16BSL-5.5 | Thread M16×1.5; cable OD 3-5.5mm; C1 thread OD 16mm; C2 thread length 15mm; spanner A/CF 22/19mm |
| 16B-10 | Thread M16×1.5; cable OD 6-10mm; C1 thread OD 16mm; C2 thread length 9mm; spanner A/CF 24/22mm |
| 16B-7 | Thread M16×1.5; cable OD 4-7mm; C1 thread OD 16mm; C2 thread length 9mm; spanner A/CF 24/22mm |
| 16BL-10 | Thread M16×1.5; cable OD 6-10mm; C1 thread OD 16mm; C2 thread length 15mm; spanner A/CF 24/22mm |
| 16BL-7 | Thread M16×1.5; cable OD 4-7mm; C1 thread OD 16mm; C2 thread length 15mm; spanner A/CF 24/22mm |
| 18B-10 | Thread M18×1.5; cable OD 6-10mm; C1 thread OD 18mm; C2 thread length 9mm; spanner A/CF 24/22mm |
| 18B-7 | Thread M18×1.5; cable OD 4-7mm; C1 thread OD 18mm; C2 thread length 9mm; spanner A/CF 24/22mm |
| 18BL-10 | Thread M18×1.5; cable OD 6-10mm; C1 thread OD 18mm; C2 thread length 15mm; spanner A/CF 24/22mm |
| 18BL-7 | Thread M18×1.5; cable OD 4-7mm; C1 thread OD 18mm; C2 thread length 15mm; spanner A/CF 24/22mm |
| 20BS-12 | Thread M20×1.5; cable OD 7-12mm; C1 thread OD 20mm; C2 thread length 10mm; spanner A/CF 27/24mm |
| 20BS-9 | Thread M20×1.5; cable OD 5-9mm; C1 thread OD 20mm; C2 thread length 10mm; spanner A/CF 27/24mm |
| 20BSL-12 | Thread M20×1.5; cable OD 7-12mm; C1 thread OD 20mm; C2 thread length 15mm; spanner A/CF 27/24mm |
| 20BSL-9 | Thread M20×1.5; cable OD 5-9mm; C1 thread OD 20mm; C2 thread length 15mm; spanner A/CF 27/24mm |
| 20B-14 | Thread M20×1.5; cable OD 8.5-14mm; C1 thread OD 20mm; C2 thread length 10mm; spanner A/CF 27/27mm |
| 20B-11 | Thread M20×1.5; cable OD 7-11mm; C1 thread OD 20mm; C2 thread length 10mm; spanner A/CF 27/27mm |
| 20BL-14 | Thread M20×1.5; cable OD 8.5-14mm; C1 thread OD 20mm; C2 thread length 15mm; spanner A/CF 27/27mm |
| 20BL-11 | Thread M20×1.5; cable OD 7-11mm; C1 thread OD 20mm; C2 thread length 15mm; spanner A/CF 27/27mm |
| 25B-18 | Thread M25×1.5; cable OD 12-18mm; C1 thread OD 25mm; C2 thread length 12mm; spanner A/CF 33/33mm |
| 25B-16 | Thread M25×1.5; cable OD 11-16mm; C1 thread OD 25mm; C2 thread length 12mm; spanner A/CF 33/33mm |
| 25BL-18 | Thread M25×1.5; cable OD 12-18mm; C1 thread OD 25mm; C2 thread length 15mm; spanner A/CF 33/33mm |
| 25BL-16 | Thread M25×1.5; cable OD 11-16mm; C1 thread OD 25mm; C2 thread length 15mm; spanner A/CF 33/33mm |
| 32B-25 | Thread M32×1.5; cable OD 18-25mm; C1 thread OD 32mm; C2 thread length 12mm; spanner A/CF 41/41mm |
| 32B-22 | Thread M32×1.5; cable OD 16-22mm; C1 thread OD 32mm; C2 thread length 12mm; spanner A/CF 41/41mm |
| 40B-32 | Thread M40×1.5; cable OD 24-32mm; C1 thread OD 40mm; C2 thread length 15mm; spanner A/CF 52/52mm |
| 40B-26 | Thread M40×1.5; cable OD 21-26mm; C1 thread OD 40mm; C2 thread length 15mm; spanner A/CF 52/52mm |
| 50B-39 | Thread M50×1.5; cable OD 31-39mm; C1 thread OD 50mm; C2 thread length 20mm; spanner A/CF 60/62mm |
| 50B-32 | Thread M50×1.5; cable OD 26-32mm; C1 thread OD 50mm; C2 thread length 20mm; spanner A/CF 60/62mm |
| 63B-44 | Thread M63×1.5; cable OD 32-44mm; C1 thread OD 63mm; C2 thread length 20mm; spanner A/CF 74/68mm |
| 63B-38 | Thread M63×1.5; cable OD 30-38mm; C1 thread OD 63mm; C2 thread length 20mm; spanner A/CF 74/68mm |
| Construction | United structure, as shown in the original A/B/C/D/F component drawing |
| Materials | A/C/F: nylon PA66; B/D: nitrile butadiene rubber (NBR) |
| Protection grade | IP68 stated in the original catalogue |
| Static temperature | -40 to+100°C; instantaneous heat resistance up to+120°C |
| Dynamic temperature | -20 to+80°C; instantaneous heat resistance up to+100°C |
| Colours | Black or grey |
| Metric thread pitch | M8×1.25; M10–M63×1.5 |
| Cable selection | Cable range describes cable outside diameter. BS/BSL/BL codes retain their distinct source dimensions; do not substitute a similar-looking item. |
Typical applications
- Metric cable-entry holes in electrical enclosures
- Control panels requiring a gland matched to cable diameter and thread length
View or download Metric united-structure original cable gland selection catalogue (PDF)
Product reference images and drawings
Original united-structure product and component drawing
Original42-item code and installation-dimension table
Match the exact cable OD range, metric thread pitch and thread length to the selected item. Installation and wiring must be performed by qualified electricians.