NewTrend · 90-degree divided-structure metric nylon cable gland
Product overview
NewTrend 90-degree divided-structure metric nylon cable glands route cable entries through a right angle. The 10 exact item codes cover M16×1.5 to M40×1.5 threads and cable outside-diameter ranges from 4–7mm to 23–33mm. Select the exact item and black or grey; each model fixes the thread and installation dimensions. The original black photograph is an M20×1.5 family illustration.
Technical selection summary
| 16A-E-7 | Thread M16×1.5; cable OD 4-7mm; C1 thread OD 16mm; C2 thread length 15mm; spanner A/CF 24/22mm |
|---|---|
| 16A-E-10 | Thread M16×1.5; cable OD 6-10mm; C1 thread OD 16mm; C2 thread length 15mm; spanner A/CF 24/22mm |
| 20A-E-11 | Thread M20×1.5; cable OD 7-11mm; C1 thread OD 20mm; C2 thread length 15mm; spanner A/CF 27/27mm |
| 20A-E-14 | Thread M20×1.5; cable OD 8-14mm; C1 thread OD 20mm; C2 thread length 15mm; spanner A/CF 27/27mm |
| 25A-E-16 | Thread M25×1.5; cable OD 12-16mm; C1 thread OD 25mm; C2 thread length 15mm; spanner A/CF 33/33mm |
| 25A-E-18 | Thread M25×1.5; cable OD 14-18mm; C1 thread OD 25mm; C2 thread length 15mm; spanner A/CF 33/33mm |
| 32A-E-22 | Thread M32×1.5; cable OD 16-22mm; C1 thread OD 32mm; C2 thread length 15mm; spanner A/CF 41/41mm |
| 32A-E-25 | Thread M32×1.5; cable OD 18-25mm; C1 thread OD 32mm; C2 thread length 15mm; spanner A/CF 41/41mm |
| 40A-E-28 | Thread M40×1.5; cable OD 20-28mm; C1 thread OD 40mm; C2 thread length 20mm; spanner A/CF 55/52mm |
| 40A-E-33 | Thread M40×1.5; cable OD 23-33mm; C1 thread OD 40mm; C2 thread length 20mm; spanner A/CF 55/52mm |
| Construction | 90-degree elbow; divided seal and claw, as shown in the original component drawing |
| Materials | A/C/E/F: nylon PA66; B/D: nitrile butadiene rubber (NBR) |
| Protection grade | IP68 stated in the original catalogue |
| Static temperature | -40 to+100°C; instantaneous heat resistance up to+120°C |
| Dynamic temperature | -20 to+80°C; instantaneous heat resistance up to+100°C |
| Colours | Black or grey |
| Cable selection | Cable range describes cable outside diameter, not conductor cross-section |
Typical applications
- Right-angle cable entries in electrical enclosures
- Control panels requiring an elbow gland matched to the cable diameter and metric mounting thread
View or download 90-degree metric divided cable glands original selection catalogue (PDF)
Product reference images and drawings
Original90-degree product and exploded component drawing
Original exact item and installation-dimension table
Match the cable outside diameter and metric thread to the selected item and component drawing. Installation and wiring must be performed by qualified electricians.