NewTrend · hum-free modular contactor
Product overview
NewTrend YMC-32/20 is a hum-free modular contactor with two normally-open main contacts in an 18mm-wide DIN-rail body. It is rated 32A for AC-7a / AC-1 loads and 12A for AC-7b / AC-3 loads, at 250VAC for this two-pole version. The factory selection table lists nominal 12V, 24V, 48V, 110V and 230V AC/DC coil versions. This page covers the /20 contact arrangement only.
Technical selection summary
| Model / contact code | YMC-32/20 |
|---|---|
| Main contact arrangement | 2P / 2NO |
| Rated current, AC-7a / AC-1 | 32A |
| Rated current, AC-7b / AC-3 | 12A |
| Rated operating voltage | 250VAC for this 2P configuration |
| Main-circuit frequency | 50/60Hz |
| Selectable coil versions | 12V / 24V / 48V / 110V / 230V AC/DC |
| Main terminals | 1–2 and 3–4 |
| Control terminals | A1–A2 |
| Rated insulation voltage | 500VAC |
| Rated impulse withstand voltage | 2.5kV; 4kV for 12/24/48VAC versions |
| Pollution degree | 2 |
| Mechanical durability | 1,000,000 cycles |
| Electrical durability | 100,000 cycles |
| Maximum switching operations | 100 per day |
| Enclosure protection | IP20 device only; IP40 in a matching modular enclosure |
| Operating temperature | -5 to +60°C |
| Storage temperature | -40 to +70°C |
| Tropicalization | Treatment 2; 95% relative humidity at 55°C |
| Mounting | 35mm DIN rail; ±30° from vertical |
| Spacer condition | Use a spacer between adjacent units at 50–60°C internal enclosure temperature |
| Overall dimensions (W×D×H) | 18×68×85.5mm; see original dimension tolerances |
| Coil consumption, 230VAC 50Hz reference | Holding 2.1VA / pull-in 2.1VA / maximum power 2.0W |
| Control and power terminal torque, 32A | 0.8N·m |
| Wire stripping length, 32A | 9mm |
| Power conductors, 16–32A versions | Rigid copper 1.5–6mm²; flexible/ferrule copper 1–4mm² |
Operation
- Apply the nominal voltage of the selected AC/DC coil version to terminals A1–A2. The five voltage choices represent separate factory versions.
- Main contacts 1–2 and 3–4 are normally open. Use the AC-7b / AC-3 current rating when selecting applicable motor loads.
- Use a spacer between adjacent contactors when the temperature inside the enclosure is 50–60°C.
Typical applications
- Lighting and resistive-heating control in building distribution boards
- Ventilation, pumps and domestic-type motor loads selected by the AC-7b rating
- Modular DIN-rail load switching controlled by a timer or automation output
View or download YMC original contactor selection, technical data and dimensions (PDF)
Product reference images and drawings
Original 2P YMC contactor selection and contact circuits
Original 4P family contact configurations
Original coil consumption, by poles and AC230V reference
Original accessories, operating limits and protection
Original family packing information
Original terminal connection data
Original contactor and auxiliary dimensions
This page covers YMC-32/20, 2P 2NO. The product photograph shows the 230V AC/DC coil example and retains its original technical markings. Other pole/contact arrangements in the family PDF are separate configurations. Installation and wiring must be performed by qualified electricians.