NewTrend · Current monitoring relay
Product overview
NewTrend RI8-05B monitors AC or DC current through an isolated sensing aperture. Its front potentiometer sets the threshold from 2 to 20A, and the Y1-Y2 jumper selects overcurrent or undercurrent monitoring. The current-direction arrow identifies conductor routing through the sensing aperture. It uses AC/DC 24-240V and provides one SPDT output rated 10A AC-1 in an 18mm DIN-rail body.
Technical selection summary
| Model | RI8-05B |
|---|---|
| Function | Overcurrent or undercurrent monitoring selected by Y1-Y2 jumper |
| Monitored current | AC 50Hz or DC |
| Current threshold range | Adjustable 2-20A |
| Measurement method | Through-hole current sensor; observe direction arrow |
| Sensing aperture | 8mm diameter |
| Control supply | AC/DC 24-240V, 50/60Hz or DC |
| Supply terminals | A1-A2 |
| Power input | Maximum 1.5VA |
| Supply tolerance | -15% to +10% |
| Threshold adjustment | Front potentiometer |
| Response delay | 0.1 second maximum |
| Supply indication | Green LED |
| Setting accuracy | 10% |
| Hysteresis | 5% |
| Mode jumper terminals | Y1-Y2 |
| Output contacts | 1 SPDT; 11-12-14 |
| Contact rating | 10A, AC-1 |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Output indication | Red LED |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | DIN rail to EN/IEC 60715; 18mm module |
| Protection | IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Maximum conductor size | 1 x 2.5mm² or 2 x 1.5mm² |
| Terminal tightening torque | 0.8Nm |
| Body dimensions | 90 x 18 x 64mm |
| Overall dimensions in drawing | 95mm overall height; 88mm depth including sensor |
| Weight | 64g |
| Referenced standard | EN 60255-1 |
Operation
- Route the monitored conductor through the current-sensing aperture and observe its direction arrow. The RI8-05B measures AC 50Hz or DC current.
- Set the current threshold with the front potentiometer. The original timing diagram shows overcurrent monitoring with Y1-Y2 open and undercurrent monitoring with Y1-Y2 linked.
- A1-A2 supplies the relay; 11-12-14 is the changeover output. The original external-current-transformer diagram is for a suitable AC measuring circuit.
Typical applications
- AC or DC current-flow supervision in control panels
- Heating circuit and heating-cable current monitoring
- Current monitoring for motor and process circuits using a suitable external contactor
View or download RI8-05A/05B through-hole current-monitoring catalogue (PDF)
Product reference images and drawings
Original specifications and model coding
Original jumper timing, panel, wiring and complete dimensions
Follow the original Y1-Y2 jumper and contact wiring diagrams. Observe the sensing-aperture direction arrow. The body is 64mm deep; the complete RI8-05B dimension drawing includes the projecting sensor and shows 88mm overall depth. Installation and wiring must be performed by qualified electricians.