NewTrend · Anti-harmonic three-phase voltage monitoring relay
Product overview
NewTrend RV8-08X monitors phase sequence, phase failure, overvoltage, undervoltage and voltage asymmetry in a three-phase control circuit. The front Un dial selects the nominal voltage. Protection settings are fixed at +15% overvoltage, -15% undervoltage, 8% asymmetry and 2 seconds trip delay. Choose the M460 three-wire or M265 four-wire hardware version. The 18mm relay provides 1 SPDT contacts rated 10A (AC-1). Anti-harmonic design.
Technical selection summary
| Model | RV8-08X |
|---|---|
| Function | Phase sequence, phase failure, overvoltage, undervoltage and asymmetry |
| Design | Anti-harmonic type |
| Voltage-system versions | M460: 3P3W; M265: 3P4W with neutral |
| M460 rated voltage range | AC 220-460V, phase-to-phase |
| M265 rated voltage range | AC 127-265V, phase-to-neutral |
| M460 nominal-voltage dial | 220 / 230 / 240 / 380 / 400 / 415 / 440 / 460V (phase-to-phase) |
| M265 nominal-voltage dial | 127 / 132 / 138 / 220 / 230 / 240 / 254 / 265V (phase-to-neutral) |
| Overvoltage / undervoltage thresholds | Fixed +15% / -15% of selected Un |
| Asymmetry threshold | Fixed 8% |
| Trip delay | Fixed 2 seconds |
| Voltage hysteresis | 2% |
| Phase-failure value | 70% of selected Un; M460 minimum 165V |
| M460 monitoring / supply terminals | L1-L2-L3 / L1-L2 |
| M265 monitoring / supply terminals | L1-L2-L3-N / L1-N |
| Supply frequency | 45-65Hz |
| Measurement | True RMS |
| M460 measuring range | 176-552V |
| M265 measuring range | 101-318V |
| Measurement error | Maximum 1% |
| Power-up delay | 0.5 seconds |
| Reset time | 1000ms |
| Temperature coefficient | 0.05%/degree C at 20 degrees C |
| Supply / phase-state indication | Green LED |
| Output indication | Red LED |
| Output contacts | 1 SPDT |
| Contact rating | 10A (AC-1) |
| Switching voltage | 250VAC / 24VDC |
| Minimum DC breaking power | 500mW |
| Mechanical life | 10,000,000 operations |
| Electrical life (AC-1) | 100,000 operations |
| Operating temperature | -20 to +55 degrees C |
| Storage temperature | -35 to +75 degrees C |
| Mounting | DIN rail to EN/IEC 60715; 1 module |
| Protection | IP40 front panel; IP20 terminals |
| Operating position | Any |
| Overvoltage category / pollution degree | III / 2 |
| Maximum conductor size | Solid: 1 x 2.5mm2 or 2 x 1.5mm2; with sleeve: 1 x 2.5mm2 (AWG 12) |
| Body dimensions | 90 x 18 x 64mm |
| Weight | 61-66g by version |
| Terminal tightening torque | 0.8Nm |
Photograph shows 3P4W / AC 127-265V. The 08 function code has one nominal-voltage dial; its protection thresholds and trip delay are fixed.
Operation
- Set the nominal-voltage dial for the selected hardware system. Overvoltage and undervoltage thresholds are fixed at +15% and -15% of Un; voltage asymmetry is fixed at 8%.
- The 08 function code uses a fixed 2-second trip delay. Phase-failure and phase-sequence monitoring are also provided.
Typical applications
- Three-phase motor and contactor-control supervision
- Voltage-window and asymmetry supervision in industrial control panels
Specify your enquiry
For a focused quotation, include:
- Three-wire M460 or four-wire M265 system and nominal voltage
- Controlled load and required contacts
- Quantity and destination
Download NewTrend RV8-08X datasheet (PDF)
Product reference images and drawings
M460 and M265 terminal connections
Phase failure and phase sequence
Common housing dimensions; RV8-04X front view shown. Product photograph shows 3P4W / AC 127-265V.
Select the Un dial position to match the actual nominal system voltage. M460 supply uses L1-L2; M265 supply uses L1-N. The fixed 08-code thresholds are not adjustable. The connection and phase-state drawings apply to the shared terminal arrangement; the drawings do not add adjustable functions. Installation and wiring must be performed by qualified electricians.