People Electric · Residual Current Circuit Breaker
Product overview
People Electric PID-125 residual-current circuit breakers monitor the vector sum of circuit currents and disconnect on a residual-current fault. This listing covers the electromagnetic version described in the manufacturer application section. Select the correct poles, voltage, waveform type and residual sensitivity for the actual installation.
Technical selection summary
| Manufacturer / series | Original People Electric PID-125 |
|---|---|
| Published version | Electromagnetic residual-current circuit breaker; electronic versions in the shared table require separate exact confirmation |
| Poles / main voltage | 2P / AC240V; 4P / AC415V; 50/60Hz |
| Rated current | 16, 25, 32, 40, 63, 80, 100, 125A |
| Residual waveform type | A or AC; specify required type explicitly |
| Rated residual operating current | 10, 30, 100, 300, 500mA |
| Rated insulation voltage | Ui 500V |
| Residual making/breaking value | The series table lists IΔm 1250A. Confirm the exact ordered current/version and nameplate rating before coordination. |
| Conditional short-circuit value | IΔc 6000A with the specified coordinated SCPD; this is not standalone overload or short-circuit protection |
| Overcurrent coordination | Provide suitable upstream overcurrent protection and confirm the actual SCPD fuse and fault level for the installation |
| Connection / mounting | Supply from top or bottom as stated; DIN rail EN 60715, 35mm, fast-clip mounting |
| Terminals / torque | Cable or busbar connection; up to 35mm² as tabulated; 2.5Nm tightening torque |
| Protection degree / pollution | IP20; pollution degree 2 |
| Operating / storage temperature | Operating -25 to +40°C, daily average ≤35°C; storage -25 to +70°C |
| Life | Electrical 4,000 operations; mechanical 10,000 operations |
| Standard stated | IEC/EN 61008; application section states IEC 61008-1 |
An RCCB provides residual-current protection and must be coordinated with the correct overcurrent protective device. Do not interpret the 6kA conditional value as a standalone RCBO breaking rating. Confirm the exact electromagnetic Type A/AC version, current-dependent making/breaking rating, SCPD and installation dimensions before ordering.
Typical applications
- Residual-current protection in coordinated low-voltage single-phase or three-phase distribution.
- Replacement RCCBs requiring exact voltage, poles, current, waveform sensitivity and upstream protection matching.
Specify your enquiry
For a focused quotation, include:
- 2P/AC240V or 4P/AC415V, rated current, Type A/AC and residual sensitivity.
- Electromagnetic version, exact nameplate making/breaking ratings and upstream SCPD/fault level.
- Mounting dimensions, installation environment, quantity and destination.
Download People Electric PID-125 catalogue (PDF)