NewTrend LC1K0610M7 3P AC3 6A 1NO aux 220V 230V AC coil Contactor
Main | |
product or component type |
LC1K0610M7 Contactor
|
product brand |
NewTrend
|
device application |
Control
|
contactor application |
Motor control
|
Complementary | |
utilisation category |
AC-3
|
AC-4 | |
poles description |
3P
|
power pole contact composition |
3 NO
|
[Ue] rated operational voltage |
Power circuit: 690 V AC 50/60 Hz
|
Signalling circuit: <= 690 V AC 50/60 Hz | |
[Ie] rated operational current |
6 A at <= 440 V AC AC-3 for power circuit
|
control circuit type |
AC at 50/60 Hz
|
[Uc] control circuit voltage |
220…230 V AC 50/60 Hz
|
motor power kW |
1.5 kW at 220…230 V AC 50/60 Hz AC-3
|
2.2 kW at 380…415 V AC 50/60 Hz AC-3 | |
3 kW at 440 V AC 50/60 Hz AC-3 | |
3 kW at 480 V AC 50/60 Hz AC-3 | |
3 kW at 500…600 V AC 50/60 Hz AC-3 | |
3 kW at 660…690 V AC 50/60 Hz AC-3 | |
1.5 kW at 400 V AC 50/60 Hz AC-4 | |
auxiliary contact composition |
1 NO
|
[Uimp] rated impulse withstand voltage |
8 kV
|
overvoltage category |
III
|
[Ith] conventional free air thermal current |
20 A (at 50 °C) for power circuit
|
10 A (at 50 °C) for signalling circuit | |
Irms rated making capacity |
110 A AC for power circuit conforming to NF C 63-110
|
110 A AC for power circuit conforming to IEC 60947 | |
110 A AC for signalling circuit conforming to IEC 60947 | |
rated breaking capacity |
110 A at 415 V conforming to IEC 60947
|
110 A at 440 V conforming to IEC 60947 | |
80 A at 500 V conforming to IEC 60947 | |
110 A at 220…230 V conforming to IEC 60947 | |
110 A at 380…400 V conforming to IEC 60947 | |
70 A at 660…690 V conforming to IEC 60947 | |
[Icw] rated short-time withstand current |
90 A 50 °C – 1 s for power circuit
|
85 A 50 °C – 5 s for power circuit | |
80 A 50 °C – 10 s for power circuit | |
60 A 50 °C – 30 s for power circuit | |
45 A 50 °C – 1 min for power circuit | |
40 A 50 °C – 3 min for power circuit | |
20 A 50 °C – >= 15 min for power circuit | |
80 A – 1 s for signalling circuit | |
90 A – 500 ms for signalling circuit | |
110 A – 100 ms for signalling circuit | |
associated fuse rating |
25 A gG at <= 440 V for power circuit
|
25 A aM for power circuit | |
10 A gG for signalling circuit conforming to IEC 60947 | |
10 A gG for signalling circuit conforming to VDE 0660 | |
average impedance |
3 mOhm – Ith 20 A 50 Hz for power circuit
|
[Ui] rated insulation voltage |
Power circuit: 600 V conforming to UL 508
|
Power circuit: 690 V conforming to IEC 60947-4-1 | |
Signalling circuit: 690 V conforming to IEC 60947-4-1 | |
Signalling circuit: 690 V conforming to IEC 60947-5-1 | |
Signalling circuit: 600 V conforming to UL 508 | |
Power circuit: 600 V conforming to CSA C22.2 No 14 | |
Signalling circuit: 600 V conforming to CSA C22.2 No 14 | |
insulation resistance |
> 10 MOhm for signalling circuit
|
inrush power in VA |
30 VA (at 20 °C)
|
hold-in power consumption in VA |
4.5 VA (at 20 °C)
|
heat dissipation |
1.3 W
|
control circuit voltage limits |
Operational: 0.8…1.15 Uc (at <50 °C)
|
Drop-out: 0.2…0.75 Uc (at <50 °C) | |
connections – terminals |
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
|
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end | |
Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end | |
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid | |
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end | |
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end | |
maximum operating rate |
3600 cyc/h
|
auxiliary contacts type |
type instantaneous 1 NO
|
signalling circuit frequency |
<= 400 Hz
|
minimum switching current |
5 mA for signalling circuit
|
minimum switching voltage |
17 V for signalling circuit
|
mounting support |
Rail
|
Plate | |
tightening torque |
1.3 N.m – on screw clamp terminals – with screwdriver Philips No 2
|
1.3 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm | |
operating time |
10…20 ms coil de-energisation and NO opening
|
10…20 ms coil energisation and NO closing | |
safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
|
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
non overlap distance |
0.5 mm
|
mechanical durability |
10 Mcycles
|
electrical durability |
1.3 Mcycles 6 A AC-3 at Ue <= 440 V
|
mechanical robustness |
Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
|
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 | |
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 | |
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 | |
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 | |
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 | |
Vibrations contactor closed: 4 Gn, 5…300 Hz conforming to IEC 60068-2-6 | |
Vibrations contactor opened: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6 | |
height |
58 mm
|
width |
45 mm
|
depth |
57 mm
|
net weight |
0.18 kg
|
Environment | |
standards |
BS 5424
|
IEC 60947 | |
NF C 63-110 | |
VDE 0660 | |
product certifications |
CE
|
IP degree of protection |
IP2x conforming to VDE 0106
|
protective treatment |
TC conforming to IEC 60068
|
TC conforming to DIN 50016 | |
ambient air temperature for storage |
-50…80 °C
|
operating altitude |
2000 m without derating
|
flame retardance |
V1 conforming to UL 94
|
Requirement 2 conforming to NF F 16-101 | |
Requirement 2 conforming to NF F 16-102 |