NewTrend · LX1D6
Product overview
NewTrend LX1D6 AC replacement coils. Select the exact coil reference; voltage and frequency are linked rather than freely combined.
Technical selection summary
| Parameter | Specification |
|---|---|
| Fitment | Legacy D2-style LC1D40/D50/D65/D80/D95 construction; confirm physical coil before replacement |
| Scope | AC LX1D6 only. LXD1, LX1D8, LX4D6 and LX4D7 are other frame or DC coils |
| Coil consumption | 50Hz: inrush200VA, holding20VA;60Hz:220VA/22VA;dual-frequency:245VA/26VA at50Hz per original table |
| Operating range | 0.85-1.1Uc at up to55C in the retained supplier table |
| Special voltage notes | M7 at230V50Hz and Q7 at400V50Hz require mechanical-endurance coefficient0.6 per reference footnotes; M7 may be used at240V60Hz; U7 permits220-240V50Hz and240V60Hz |
| 208V code | Dual-frequency code is LX1D6LE7, corroborated by current original-brand order table; old image LC1D6LE7 is a printing error |
| Resistance / inductance | All available original rows and blank entries retained in the reference image; no missing value is invented |
NewTrend replacement supply does not inherit Schneider certification. The reference is for legacy D2-style contactors, not every modern LC1D40A/65A frame. Confirm geometry and actual contactor before fitting.
Typical applications
- Electrical panel assembly and installation