CHINT · JQX-13F
Product overview
CHINT JQX-13F is a miniature electromagnetic power relay with a transparent dust cover, AC or DC coil versions and multiple connection and mounting styles. The manufacturer catalogue reproduced below covers 2Z (two-changeover-contact) versions with a rated resistive load of 10 A at 250 VAC or 30 VDC. Select the complete relay code, coil voltage and mounting arrangement for the intended control circuit.
Technical selection summary
| Series and catalogue scope | CHINT JQX-13F; the supplied manufacturer catalogue covers 2Z (2CO) versions. |
|---|---|
| Contact arrangement | 2Z: two changeover contacts (2CO / DPDT). |
| Rated resistive load | 10 A at 250 VAC / 30 VDC. |
| Maximum switching ratings | 250 VAC / 30 VDC; 10 A; 2500 VA / 300 W. Match the load type and operating conditions. |
| Contact material / initial resistance | Silver alloy; initial contact resistance 100 mΩ. |
| Electrical / mechanical endurance | 1 × 10⁵ / 1 × 10⁷ cycles, as listed in the manufacturer catalogue. |
| Coil selection | AC and DC versions. Confirm the complete coil-voltage and version code; the full coil tables are reproduced below. |
| Rated coil consumption | 0.9 W (DC) / 1.8 VA (AC). |
| Operation / release time | Each ≤25 ms at 25°C and rated voltage. |
| Ambient temperature | −25°C to +55°C. |
| Relay body dimensions | 27.5 × 21.5 × 35.5 mm; mounting projections and flange dimensions depend on the version. See the complete drawings below. |
| Connection and mounting | Plug-in and PCB terminals; plug-in, PCB, lateral-flange and top-flange outlines are shown in the catalogue. |
| Indicator / suppression versions | D: status indicator. B: status indicator and surge suppression for DC. Blank: standard version. |
| Socket selection | Optional matching sockets are listed for JQX-13F(D)/2Z. Match the exact relay, terminal layout and installation dimensions before ordering. |
Catalogue scope: the technical data and drawings below cover JQX-13F 2Z versions, including the indicated D/B options. They do not verify 1CO, 3CO or 4CO configurations, or JQX-13FA/1Z. Confirm the complete manufacturer model and matching documentation before specifying another configuration. Resistive-load ratings must not be applied directly to motor or other inductive loads.
Typical applications
- Relay switching and signal interfacing in electrical control circuits.
- Control-panel assemblies requiring a matched coil supply, contact arrangement and connection style.