NewTrend / OEM · TCB3
Product overview
TCB3 is a plug-in thermal-magnetic circuit breaker for matching AC distribution equipment. This page covers the single-pole rows in the original NewTrend supplier catalogue.
Technical selection summary
| Current / poles | 1P: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60A |
|---|---|
| Electrical rating | AC120/240V; 50/60Hz; interrupting rating 10kA, per the exact 1P ordering table |
| Trip | Thermal-magnetic; D characteristic specified as 8–20 times In in this supplier catalogue. Do not substitute a different standard’s D-curve limits |
| Mechanical | IP30; electrical life 6,000 operations; mechanical life 10,000; plug-in incoming / tunnel outgoing terminal |
| Environment | −25 to +40°C; reference 30°C; maximum altitude 2,000m, as stated in the native page |
| Certification scope | The original catalogue references UL489. No independent UL file for this NewTrend/OEM supply is established here; an exact listing must be confirmed where required |
| Dimensions / installation | Original outline, installation, removal and conductor/torque pages retained; single-pole scope only. Catalogue parallel assemblies are not selectable configurations |
State current, panel/busbar dimensions, supply and quantity. Confirm exact approval requirements and delivered nameplate before ordering.
Verified selection table
| 10A | TCB3-10/1 |
|---|---|
| 15A | TCB3-15/1 |
| 20A | TCB3-20/1 |
| 25A | TCB3-25/1 |
| 30A | TCB3-30/1 |
| 35A | TCB3-35/1 |
| 40A | TCB3-40/1 |
| 45A | TCB3-45/1 |
| 50A | TCB3-50/1 |
| 60A | TCB3-60/1 |
Typical applications
- AC branch circuit protection in a compatible distribution panel
Open original supplier reference image