People Electric · Thermal Overload Relay
Product overview
People Electric JRS2 thermal overload relays protect compatible AC motor starter circuits against overload and phase loss. This page offers the three combined-mounting frames identified in the original photographs and manufacturer handbook, with frame-specific current intervals. Select a range containing the actual motor current and confirm the matched CJX1 contactor.
Technical selection summary
| Manufacturer / series | Original People Electric JRS2 |
|---|---|
| Published versions | JRS2-12.5/Z, JRS2-25/Z and JRS2-32/Z; Z = combined installation |
| Main-circuit ratings | AC 690V; 50/60Hz; Ui 690V |
| Trip class | 10A for these three frames |
| Reset and protection functions | Manual / automatic reset selection, overload and phase-loss protection, temperature compensation and test function |
| Auxiliary contacts | 1NC (95–96) + 1NO (97–98) |
| Auxiliary AC-15 ratings | 1.9A at 220V; 1.1A at 380V; auxiliary Ui 380V; Ith 6A |
| Matched combined contactors | JRS2-12.5: CJX1-09/-12; JRS2-25: CJX1-16/-22/-32; JRS2-32: CJX1-22/-32 |
| Control supply | Thermal relay; no independent contactor-coil voltage is required |
| Environment | −5 to +40°C; daily average ≤35°C; altitude ≤2000m; pollution degree 3; installation category III |
| Standards stated | GB 14048.4; IEC 60947-4-1 |
| Coordination | Provide separately coordinated short-circuit protection; consult the handbook conductor and SCPD tables |
| JRS2-12.5/Z intervals | 0.16–0.25A, 0.25–0.4A, 0.5–0.63A, 0.63–1A, 0.8–1.25A, 1–1.6A, 1.25–2A, 1.6–2.5A, 2–3.2A, 2.5–4A, 3.2–5A, 5–8A, 6.3–10A, 8–12.5A, 0.32–0.5A, 4–6.3A, 10–14.5A |
| JRS2-25/Z intervals | 0.16–0.25A, 0.25–0.4A, 0.5–0.63A, 0.63–1A, 0.8–1.25A, 1–1.6A, 1.25–2A, 1.6–2.5A, 2–3.2A, 2.5–4A, 3.2–5A, 5–8A, 6.3–10A, 8–12.5A, 10–16A, 12.5–20A, 16–25A |
| JRS2-32/Z intervals | 4–6.3A, 6.3–10A, 10–16A, 12.5–20A, 16–25A, 20–32A, 25–36A |
Only the documented combined-mounting frames and intervals shown in the selectors are offered. The ambiguous 0.1–016A entry and the 4–6.3A table row containing an unlisted frame code are excluded for affected frames. Larger-frame trip-class and frame-code discrepancies are not carried into this listing. Photos are original series examples; confirm the exact current interval and matched contactor before ordering.
Typical applications
- Overload and phase-loss protection of compatible AC motor starters.
Specify your enquiry
For a focused quotation, include:
- Exact JRS2 frame/mounting code and current setting interval.
- Motor current, actual voltage/frequency, matched CJX1 contactor and reset requirements.
- Quantity, auxiliary-contact duty, destination and documentation.
Download People Electric JRS2 catalogue (PDF)