NewTrend · NH / NT Base
Product overview
NewTrend NH/NT ceramic fuse bases. Select the exact base size and confirmed AC voltage; the base current follows its size.
Technical selection summary
| Parameter | Specification |
|---|---|
| Product | Single-pole ceramic fuse bases; fuse links selected separately |
| Base / current | NH00/NH0:160A;NH1:250A;NH2:400A;NH3:630A;NH4:1000A |
| Voltage | AC500V / AC690V actual base supply confirmed |
| Mounting | Screw mounting for the selected ceramic bases |
| Dimensions | Exact ceramic outlines and dimensions retained in original table |
| Coordination | No independent120kA breaking capacity is assigned to a base |
| Other variants | NH00T and K/P mounting versions remain source references; not freely interchanged with ceramic plain-base selection |
Base rated current is not the selected fuse-link current or an independent interrupting rating. The owner confirms AC500/690V supply. Previous1250/1600A fuse-link confirmations do not increase this source NH4 base beyond1000A.
Typical applications
- Mounting and replacement of matching NH/NT fuse links
Open technical reference image