NewTrend · MC-40a
Product overview
Series illustration: retained photo showsMC-32a. Actual selected NewTrend reference model and coil supply are shown by the options.
Technical selection summary
| Parameter | Specification |
|---|---|
| Supply identity | NewTrend/OEM;original LS specifications used as authorised reference,not LS-branded supply |
| Main circuit | 3P,3NO;AC-3 40A atAC380-440V |
| Other voltage-specificAC-3 ratings | 40A atAC200-240V;32A atAC500-550V;23A atAC690V |
| Thermal currentAC-1 | 60A |
| Coil supply | AC50Hz,AC60Hz,AC50/60Hz orDC;voltage options linked to supply type |
| Coil voltage tolerance | 85-110%Uc per original reference |
| Main-circuit maximumUe | AC690V;Ui1000V/Uimp8kV for40a,Ui690V/Uimp6kV for12a/12b |
| Coil consumption reference | 40a:AC90VA inrush/9VA holding,DC9W;12a/12b:AC70VA inrush/9VA holding,DC5W;conditions in original coil table |
| Auxiliary contacts | 40a:2NO+2NC;12a:1NO or1NC;12b:1NO+1NC |
| Outline per original page tableW xH xD | MC40a:AC69 x83 x93mm,DC69 x83 x120mm |
| Reference-version limitation | LS catalogue revisions have different frame outlines. The retained original product-page table governs its reference outline;confirm the supplied unit before drilling or fitting accessories |
| Mounting / accessories | DIN rail or screw mounting as appropriate to supplied construction;side/front auxiliary blocks and surge suppressors separate |
Main-circuitAC switching and AC/DC coil supply are different specifications. Coil voltage and frequency are linked,not freely combined. No LS certification,short-circuit coordination or universal accessory compatibility is inherited.
Typical applications
- Electrical panel assembly and installation