DELIXI · Operator controls
Product overview
LA4 protective two-button control station, corresponding to the LA4-2H construction in the manufacturer report and the red/green enclosure photograph.
Technical selection summary
| Thermal current / insulation | Ith5A; Ui380V; Uimp6kV.5A is a thermal rating, not the AC-15 switched-load current. |
|---|---|
| Control-load ratings | AC-15: AC380V0.8A. DC-13: DC220V0.3A, per original manufacturer manual/report. |
| Enclosure / outline | Protective version IP20; two-button enclosure74±2×120±2×65±2mm. Vertical fixing centres104±0.31mm, horizontal30±0.35mm,2ר6; see full original drawing and gland information. |
| Connections | Copper0.5–1.5mm²; terminal tightening torque1.2N·m. Use the original installation and wiring guidance. |
| Outstanding contact configuration | The exact supplied red/green NO/NC contact arrangement and return action are not established by the catalogue colour guidance. Confirm the unit contact markings; no invented1NO+1NC combination is selectable. |
This is a control station, not a motor starter or a5A motor-load switch. Verify the contact block markings and required stop/start logic before ordering.