CNC Electric · YCQR2
Product overview
The YCQR2-045 soft starter provides controlled starting and stopping of a compatible 45kW three-phase AC squirrel-cage motor. Microprocessor-controlled thyristors limit starting current or ramp the applied voltage, then transfer operation to a bypass contactor.
Technical selection summary
| Brand | CNC Electric |
|---|---|
| Model | YCQR2-045 |
| Motor power | 45kW |
| Rated working current | 80A |
| Rated working voltage | AC380V ±15% |
| Frequency | 50Hz |
| Control supply | AC220–240V, 50Hz |
| Starting modes | Current-limit starting or voltage-ramp starting |
| Initial voltage | 30–80%; factory 30% |
| Ramp-up time | 0–60s; factory 10s |
| Soft-stop time | 0–60s; factory 2s; 0 means free stop |
| Starting-current limit | 150–500%; factory 250%; voltage mode retains a 400% limit |
| Start / interlock delay | 0–240s |
| Control / signals | Keypad, external or PC control; RS485; 0–20mA analogue output; fault and bypass relay outputs |
| Protection | Overcurrent, overload, thermal and phase-loss protection |
| Outline dimensions A×B×C | 265×154×165mm |
| Mounting centres / holes | 219×140mm; Ø6mm |
Selection and installation
The original wiring diagram shows an external bypass contactor and its relay output, the separate 220V control supply and the RUN/STOP/COM control terminals. Provide coordinated motor protection and size the bypass contactor and wiring for the motor duty. This is a starter for line-frequency motor operation; it does not provide variable-speed control. The 45kW model uses the compact 5.5–55kW housing dimensions shown below.
Typical applications
Compatible pumps, fans and other AC motor drives requiring reduced starting impact; industrial line-frequency motor starting.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.