CNC Electric · YCL8-02
Product overview
The CNC Electric YCL8-02 monitors conductive liquid levels in wells, reservoirs and tanks. This original YCL8-02 version provides selectable one-level or two-level, pump-up / pump-down, AC/DC24–240V isolated supply and a 10A AC-1 changeover output.
Technical selection summary
| Manufacturer model | YCL8-02 |
|---|---|
| Control function | Selectable one-level or two-level, pump-up / pump-down |
| Supply / frequency | AC/DC24–240V; 50/60Hz AC |
| Input power / tolerance | Maximum 2VA; −15% / +10% |
| Sensitivity | 5–100kΩ, adjustable |
| Electrode voltage / current | Maximum AC5V / AC <0.1mA |
| Response time | Maximum 400ms; 02 output delay adjustable 0.1–10s |
| Output | 1CO (SPDT), 10A AC-1 |
| Switching voltage | 250V AC / 24V DC |
| Probe cable limits | 800m / 400nF at 25kΩ; 200m / 100nF at 100kΩ |
| Ambient / protection | −20°C to +55°C; IP40 front / IP20 terminals |
| Mounting / dimensions | 35mm DIN rail; 90 × 18 × 64mm nominal; original outline includes 95mm terminal extremity |
| Conductor / torque | Solid 1 × 2.5 or 2 × 1.5mm²; 0.8N·m |
Selection and installation
The original YCL8 instructions, front-panel drawing and function diagrams identify YCL8-01 (one sensitivity dial) and YCL8-02 (function, sensitivity and time dials). The current webpage HTML incorrectly shifts these headers to 02/03; that header is not used. Use conductive-liquid electrodes and the exact model wiring; electrodes and pumps are not included. The 10A AC-1 rating is for the control contact, not a pump-motor starting rating. 02 selects pump-up/down and one/two levels, with 0.1–10s adjustable output delay.
Typical applications
Conductive-liquid level sensing in tank filling, draining and pump-control systems, using an appropriately rated external contactor.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.


