CNC Electric · YCB9ZF-100AP
Product overview
The YCB9ZF-100AP combines motorized circuit switching, local OLED monitoring and configurable protection with an RS485 interface. It records electrical measurements, switching events and energy usage for connected distribution systems. This is the 100AP monitoring and leakage-protection version.
Technical selection summary
| Brand | CNC Electric |
|---|---|
| Model | YCB9ZF-100AP |
| Pole versions | 1P+N and 3P+N; catalogue dimension drawings labelled 2P and 4P |
| Rated current | 63A or 100A in the model-specific table |
| Rated voltage | Single phase AC230V; three phase AC400V, according to the LVD verification and product marking |
| Frequency | 50/60Hz |
| Trip characteristic / Icn | C curve; 6kA |
| Residual-current setting | 30–500mA; leakage trip within 100ms |
| Rated-current setting | 1A to 1×In |
| Overvoltage / undervoltage | 250–320V / 100–200V; default 3s delay, adjustable 0–99s |
| Overtemperature | Adjustable 0–120°C; delay adjustable 0–99s |
| Local display | 1.3-inch OLED; Chinese / English menus |
| Monitoring | Voltage, current, leakage current, temperature, active/reactive/apparent power, power factor and accumulated energy |
| Communication | RS485 standard; DL/T-645 / Modbus in non-gateway mode; optional 4G, Wi-Fi, NB and RJ45 configurations |
| Scheduling / events | 5 timing groups; 680 locally queryable switch-event logs |
| Operating time | Closing <1.5s; opening <1s |
| Endurance | Electrical >6000 operations; mechanical >20,000 operations |
| Protection degree | IP20 |
| Dimensions | 2P width 72mm; 4P width 108mm; overall height 123.5mm; see original drawing for tolerances |
Selection and installation
LVD verification CLZJ24032656228 lists EN61009-1:2012/A13:2021 and AC230/400V. The older shared catalogue prints AC440V; this page follows the verification and product marking. The selections below use the catalogue-specific 63A and 100A versions and standard RS485 communication. Optional communication hardware is a separate configuration and is not implied by the standard unit. The catalogue includes both 100AP and 100W; the 100AP functions and drawings apply to this page. Use the maintenance safety lock and isolate the supply before service. Installation and communication setup require a qualified electrician.
Typical applications
Building and industrial distribution monitoring; energy metering with remote switching; scheduled operation and event logging.
Original technical data and drawings
The following manufacturer figures retain the original technical content. Dimensions are in millimetres unless otherwise marked. Refer to the model and frame labels when using a shared family drawing.
Download the complete original CNC YCB9ZF-100AP catalogue (PDF)