CHINT · Modular RCBO
Product overview
CHINT 540139 NXBLE-63YH 4P D32 300mA Type A 6kA is a modular residual current operated circuit-breaker with overcurrent protection (RCBO). This ordering code is the 4P, 32 A, D-curve, 300 mA Type A version, with a rated voltage of 400 V AC, in accordance with IEC/EN 61009-1, IEC 61009-2-2, GOST IEC 61009-1-2020. Its rated short-circuit breaking capacity (Icu) is 6 kA. The residual-current function is electronic.
Technical selection summary
| Ordering code | 540139 |
|---|---|
| Manufacturer model | NXBLE-63YH 4P D32 300mA Type A 6kA |
| Product type | Modular RCBO (residual current operated circuit-breaker with overcurrent protection) |
| Reference standard | IEC/EN 61009-1; IEC 61009-2-2; GOST IEC 61009-1-2020 |
| Poles | 4P |
| Rated current In | 32 A |
| Trip curve | D |
| Rated residual operating current IΔn | 300 mA |
| Residual current type | Type A |
| Rated voltage Ue | 400 V AC |
| Rated frequency | 50/60 Hz |
| Rated short-circuit breaking capacity (Icu) | 6 kA |
| Service breaking capacity (Ics) | 6 kA |
| Rated insulation voltage Ui | 500 V |
| Rated impulse voltage Uimp | 4 kV |
| Degree of protection | IP20 |
| Pollution degree | 2 |
| Operating temperature | −35 to +70 °C |
| Mechanical life | 10,000 operations |
| Electrical life | 20,000 operations |
| Device construction | Electronic |
| Overall dimensions (W × H × D) | 90 × 92.5 × 78 mm |
| Mounting | 35 mm DIN rail |
Product features
- Combined residual-current, overload and short-circuit protection in one modular device.
- Electronic Type A residual-current function, D-curve overcurrent release, 4P, 32 A, 300 mA, 6 kA.
- 35 mm DIN-rail mounting, with a test button and ON/OFF position indication as shown on the official product page.
Typical applications
- Low-voltage distribution circuits requiring residual-current, overload and short-circuit protection.