CHINT · Motor Protection Circuit Breaker
Product overview
CHINT 495082 NS2-25/1F is a three-pole motor protection circuit breaker with a 9–14 A adjustable thermal setting and rocker on/off control. It provides motor switching with overload and short-circuit protection.
Technical selection summary
| Ordering code | 495082 |
|---|---|
| Manufacturer model | NS2-25/1F |
| Reference standard | IEC/EN 60947-2 |
| Poles | 3P |
| Rated current (In) | 14 A |
| Rated voltage | 230/400/690 V AC |
| Frequency | 50/60 Hz |
| Insulation voltage (Ui) | 690 V AC |
| Impulse withstand voltage (Uimp) | 8 kV |
| Maximum operating voltage | 690 V AC |
| Ultimate breaking capacity (Icu) | 15 kA — verify at actual operating voltage |
| Service breaking capacity (Ics) | 7.5 kA — verify at actual operating voltage |
| DIN modules | 2.5 |
| Ingress protection | IP20 |
| Dimensions (H × W × D) | 91.3×44.5×80.8 mm |
| AC-3 motor power at 230V | 3 kW |
| AC-3 motor power at 400V | 5.5 kW |
| AC-3 motor power at 690V | 9 kW |
| Current adjustment (Ir) | 9–14 A |
| Control | Rocker ON/OFF |
| Units per pack | 1 |
| Units per carton | 60 |
| EAN | 6925808307905 |
| Ambient temperature | −5 to +40 °C |
| Maximum altitude | 2,000 m |
Confirm Icu and Ics for the actual system voltage against the supplied unit’s nameplate before selection.
Typical applications
- Machine motor feeders
- Pump and fan motor protection
- Manual motor control panels