CHINT · Molded Case Circuit Breaker
Product overview
CHINT 263079 is a 4-pole thermal-magnetic molded case circuit breaker for industrial AC distribution. The 1600 A frame contains a 1000 A release for overload and short-circuit protection.
Model and trip unit
NM8N-1600S-1000/4/25 identifies the 1600 A frame, S breaking-capacity class, 1000 A rated current and 4-pole Frame 25 configuration. The thermal adjustment for this code is 0.8 – 1 x In.
Technical selection summary
| Ordering code | 263079 |
|---|---|
| Manufacturer model | NM8N-1600S-1000/4/25 |
| Standard | EN 60947-2 |
| Poles | 4P |
| Rated current (In) | 1000 A |
| Rated voltage | 380/415 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Impulse withstand voltage (Uimp) | 8 kV |
| Maximum operating voltage | 690 V AC |
| Ultimate breaking capacity (Icu) | 50 kA (AC380/400/415V) |
| Service breaking capacity (Ics) | 50 kA (AC380/400/415V) |
| Power dissipation | 320 W |
| Degree of protection | IP00 / IP40 with terminal covers |
| Dimensions (H × W × D) | 286x280x167 mm |
| Thermal adjustment (Ir) | 0.8 – 1 x In |
| Utilization category | A |
| Trip unit | Thermal-magnetic |
| Frame designation | Frame 25 |
| Units per pack | 1 |
| Units per carton | 1 |
| EAN | 6932103861315 |
| ETIM | EC000228 |
Short-circuit ratings by voltage
| Operating voltage | Icu | Ics |
|---|---|---|
| 380 / 400 / 415 V AC | 50 kA | 50 kA |
| 440 V AC | 50 kA | 40 kA |
| 500 V AC | 40 kA | 30 kA |
| 660 / 690 V AC | 30 kA | 30 kA |
Typical applications
- Industrial power distribution panels and power centers
- Feeder protection in motor control centers
Download CHINT NM8N series catalogue (PDF)