CHINT · Surge protective device
Product overview
CHINT 252536 NU6-IIG/F is a Type 2 surge protective device with a 2P connection arrangement and remote fault signalling. This 320 V AC version has a maximum discharge current of 65 kA and a nominal discharge current of 30 kA at an 8/20 µs waveform.
Technical selection summary
| Ordering code | 252536 |
|---|---|
| Manufacturer model | NU6-IIG/F 65/320 2P |
| SPD test class | Type 2 / Class II |
| Poles | 2P |
| Maximum continuous operating voltage Uc | 320 V AC |
| Maximum discharge current Imax (8/20 µs) | 65 kA |
| Nominal discharge current In (8/20 µs) | 30 kA |
| Voltage protection level Up | 1.8 kV |
| Remote signalling | Yes; 1NO+1NC changeover contact |
| Auxiliary contact rating | 250 V AC, 0.5 A |
| Frequency | 50/60 Hz |
| Cartridge status indication | Green: OK; red: fault |
| Construction | Removable protective cartridges and base |
| Reference standard | IEC/EN 61643-11 |
Product features
- Removable protective cartridges with a visual status window.
- Remote changeover contact for external status monitoring.
- Modular construction for low-voltage distribution panels.
Typical applications
- Building distribution panels and sub-panels.
- Protection of sensitive electrical equipment against transient overvoltage.
- Industrial low-voltage distribution circuits with the corresponding earthing arrangement.