CHINT · HVACR Definite Purpose Contactor
Product overview
CHINT 245428 NCK3-40/1 is a 1-pole definite purpose contactor with a 380 V AC, 50 Hz coil for HVACR control. It is the 40 A ordering specification with 1 normally open main contact and no auxiliary contacts. The main-circuit FLA, RES and LRA ratings are listed separately for the applicable load voltage.
Technical selection summary
| Ordering code | 245428 |
|---|---|
| Manufacturer model | NCK3-40/1 |
| Ordering current (AC-8a) | 40 A |
| Main contacts | 1P (1NO) |
| Auxiliary contacts | None |
| Coil voltage | 380 V AC |
| Coil frequency | 50 Hz |
| Certification | UL Recognized (E205608) |
| Utilization category | AC-1 / AC-8a |
| Full-load current (FLA) | 40 A at 240/277, 480 and 600 V AC |
| Resistive load current (RES) | 50 A |
| Locked-rotor current (LRA) | 240 A at 240/277 V; 200 A at 480 V; 160 A at 600 V |
| Single-phase motor rating | 1 HP at 120 V; 3 HP at 240 V |
| Rated insulation voltage (Ui) | 630 V |
| Degree of protection | IP00 |
| Dimensions (H × W × D) | 92 × 55 × 67 mm maximum |
| Ambient temperature | −5 to +40 °C |
| Altitude | Up to 2,000 m |
| Pollution degree | 2 |
| Mounting inclination | Within ±5° of the vertical plane |
| Reference standards | UL/CSA 60947-4-1; IEC/EN 60947-4-1 |
Product features
- 1-pole switching for definite purpose HVACR applications.
- 380 V AC coil for 50 Hz control circuits.
- Compact open construction with screw and quick-connect terminal arrangements.
- Separate full-load, resistive-load and locked-rotor ratings for equipment selection.
HVACR switching
NCK3 contactors are used for switching compressor, refrigeration, heating and ventilation loads. Match the main contacts to the load voltage and its running and starting current. The coil voltage refers to the control circuit and is separate from the switched load voltage.
Typical applications
- Air conditioner condensing units and chillers.
- Heat pump and refrigeration compressor controls.
- Commercial electric heating and fan controls.